Dip Switches - Kohler 20-2250 kW Operation

Industrial generator sets
Table of Contents

Advertisement

1.2.7

DIP Switches

The controller circuit board contains eight DIP switches,
see Figure 1-9.
DIP
Switch Description
1
Overspeed selection
2
Temperature Cooldown
Enable
3
Crank Mode Selection
4
Engine Comm. Setting
5
Engine Comm. Setting
6
Modbusr Address Bit 0
7
Modbusr Address Bit 1
8
Modbusr Address Bit 2
4
No ECM
5
4
MDEC/ADEC Comm.
5
Isochronous
4
J1939 Communication
5
4
MDEC/ADEC Comm.
5
Governor (VSG)
(Doosan, GM, and
Volvo engine only)
Figure 1-9 DIP Switch Functions
Note: After setting DIP switches to the generator set
application, be sure to power down and then
power up the controller (disconnect the battery
and then reconnect the battery of the generator
set) or use the prime power switch, if equipped.
The controller will NOT acknowledge the DIP
switch change until after generator set controller
is powered up.
Push down the end of the DIP switch near the OPEN
label to open the switch, or push down the other end to
close it. See Figure 1-10.
1
2 3
1. Push this side down to open circuit.
Figure 1-10 DIP Switch Open Position
Modbusr is a registered trademark of Schneider Electric.
TP-6161
1/12
Switch Position
Open
Closed
60 Hz
70 Hz
Cooldown
Cooldown
Disabled
Functional
Cyclic
Continuous
See selections for
DIP switch 4 and
DIP switch 5 below
Value = 0
Value = 2
Value = 0
Value = 4
Value = 0
Value = 8
Open
Open
Closed
Open
Open
Closed
Closed
Closed
4 5 6 7 8
OPEN
Typically, the factory default settings have all the DIP
switches in the closed position except the crank mode
selection switch SW3 which is open for cyclic cranking.
The overspeed selection switch SW1 is open on 50 Hz.
units.
Be sure to select the correct DIP switch
configuration for each generator set application.
Overspeed Frequency (DIP Switch 1). The generator
set overspeed frequency is set using DIP switch 1.
Select 70 Hz for 60 Hz voltages and 60 Hz for 50 Hz
voltages.
Temperature Cooldown (DIP Switch 2).
generator set will continue to run during a five-minute
cooldown cycle or shut down immediately. The choice is
made using DIP switch 2.
Engine Cranking (DIP Switch 3). The controller is
factory-set for cyclic cranking.
continuous cranking mode, use DIP switch 3.
Engine Configuration (DIP Switches 4 and 5). See
Figure 1-9 for the DIP switch positions based on engine
configurations regarding non-ECM, MDEC, and J1939
engine communication selections.
Modbusr Address (DIP Switches 6- -8).
Modbusr device requires a unique address. Address
numbers are created using a binary number system with
DIP switches 6--8. Figure 1-11 shows the DIP switch
position for each address number.
Modbusr
Address
1
3
5
7
9
11
13
15
Figure 1-11 Modbusr Device Address
1
6126
To change to the
DIP Switches
6
7
Value = 2
Value = 4
Open
Open
Closed
Open
Open
Closed
Closed
Closed
Open
Open
Closed
Open
Open
Closed
Closed
Closed
Section 1 Specifications and Features
The
Each
8
Value = 8
Open
Open
Open
Open
Closed
Closed
Closed
Closed
15