Airflow Charts; Indoor Airflow Data; Fresh Air Door - Friedrich 000 BTU'S Service Manual

Vert-i-pak a series single package vertical air conditioning system
Table of Contents

Advertisement

EXAMPLE: Measured voltage to unit (heaters) is 230 volts.
Measured Current Draw of strip heaters is 11.0 amps.
230 x 11.0 = 2530
2530/1000 = 2.53 Kilowatts
2.53 x 3413 = 8635
Supply Air
95
Return Air
75
Temperature Rise
20
20 x 1.08 = 21.6
8635
= 400 CFM
21.6

Indoor Airflow Data

The Vert-I-Pak A series units must be installed with a free
return air configuration. The table below lists the indoor
airflow at corresponding static pressures. All units are rarted
at low speed.
The Vert-I-Pak units are designed for either single speed or
two fan speed operation. For single speed operation refer to
the airflow table below and select the most appropriate CFM
based on the ESP level. Connect the fan output from the
thermostat to the unit on either the GL terminal for low speed
or to the GH terminal for high speed operation.
For thermostats with two-speed fan outputs connect the low
speed output to the unit GL terminal and the high speed
output to the GH terminal.
Ductwork Preparation
Duct ESP:
To determine your system's indoor external static pressure
(ESP, in inches of water) use a duct calculator (as provided
by your duct supplier). Include all flex duct transitions and
discharge grille(s). If flex duct is used, be sure all the slack
is pulled out of the flex duct. Flex duct ESP can increase
considerably when not fully extended. DO NOT EXCEED a
total of .30 ESP, as this is the MAXIMUM design limit for the
VERT-I-PAK A-Series unit.
Ductwork Preparation
Pull the fl ex duct tight. Extra fl ex duct slack can greatly
increase static pressure
IMPORTANT: FLEX DUCT CAN COLLAPSE AND
CAUSE AIRFLOW RESTRICTIONS. DO NOT
USE FLEX DUCT FOR: 90 DEGREE BENDS, OR
UNSUPPORTED RUNS OF 5 FT. OR MORE.
F
°
F
°
°
Determining the Indoor CFM: Chart A – CFM
VEA09/VHA09
ESP (")
Low
High
.00"
340
385
.10"
300
340
.20"
230
280
.30"
140
190
Highlighted values indicate rated performance point.
Rated performance for
*
VEA12
Rated Performance for
**
VHA12
VEA24/VHA24
ESP (")
Low
.00"
690
.10"
610
.20"
560
.30"
510
.40"
450
Highlighted values indicate rated performance point.
Correct CFM (if needed):
Chart B – Correction Multipli
Explanation of charts
Chart A is the nominal dry coil VERT-I-PAK CFMs. Chart
B is the correction factors beyond nominal conditions.

Fresh Air Door

The Fresh Air Door is an "intake" system. The fresh air door
opened via a slide on the front of the chassis located just
above the indoor coil. Move the slide left to open and right
to close the fresh air door. The system is capable of up to 60
CFM of fresh air @ ~.3" H20 internal static pressure.
Model
VEA12/VHA12
VEA18/VHA18
Low
High
Low
420
470
430
350 *
420 **
400
290
350
340
250
300
290
Model
High
740
700
640
580
520
ers
High
480
450
400
330
21