Eaton 5PX Advanced User's Manual page 21

Hide thumbs Also See for 5PX:
Table of Contents

Advertisement

Submenu
Forced
reboot+
timer?
Energy saving
(W,%, delay)
Sleep Mode +
timer
Site Wiring
Fault
Power Off
alert
Auto battery
test
Battery life
Battery
warning
settings
Low battery
warning
(capacity +
remain. time)
614-40099-00
Available settings
[Yes] [No]
[Timer] [10s] ... [180s]
When mains recovers during a shutdown sequence:
If set to Enabled, shutdown sequence will complete and
wait 10 seconds prior to restart,
If set to Disabled, shutdown sequence will not complete,
UPS stays on.
[Yes] [No]
[Time] [1min] ... [15min]
[Level] [10W] ... [1000W-3000W]
If Enabled, UPS will shut-down after defined duration. of
back-up time, if load is less than set value.
[Enabled] [Disabled]
[Timer] [10min] ... [120min]
If Disabled, LCD and communication will turn OFF
immediately after UPS is OFF.
If Enabled, LCD and communication stays ON for the set
time period after UPS is OFF (default 90 min).
[Enabled] [Disabled]
Prevents from starting the UPS in case of phase vs neutral
wires swapping.
[Yes] [No]
If Enabled, activates a confirmation screen that requires
user confirmation after pressing the power button, before
UPS shutdown occurs.
In ABM® cycling mode: [No test] [Every ABM® cycle]
In constant charge mode: [No test] [Daily] [Weekly]
[Monthly]
[Enabled] [Disabled]
[6-120]
Battery Age warning
If Enabled, the UPS displays a battery replacement
reminder through the front LCD and any installed network
communication card after the indicated timeframe has
elapsed (default 48 months).
[Capacity] [0%] ... [100%]
[Runtime] [0min] ... [60min]
The alarm triggers when the set percentage of battery
capacity or remaining back-up time is reached.
Default settings
[Yes]
[10s]
[No]
[5min]
[100W]
[Enabled]
[90min]
[Disabled]
[Yes]
[Every ABM® cycle]
[Monthly]
[Enable]
[48 Month]
[20%]
[3min]
21