Modbus Errors
Modbus errors are typical protocol errors defined by fieldbus specification. The fieldbus error code shown is returned
to the PLC when the error condition occurs.
Code
Name
1
Illegal Function
2
Illegal Data Address
3
Illegal Data Value
4
Slave Device Fail
5
Acknowledge
6
Slave Device Busy
8
Memory Parity Error
10
Gatweay Path Unavailable
11
Gateway Target Fail
255
334183B
Cause
Request function is not supported. Use supported Modbus functions:
Exceeded maximum register count
of 121 registers.
No valid property mapped to the
requested Modbus register.
Write Holding Register(s) returns
set property error.
An active system error exists.
Unspecified
Solution
Read Holding Register
Write Holding Register
Write Multiple Holding Registers
Request 121 or fewer registers at a time.
Verify that the device has valid mapping.
See MBTCP Modbus Error for 4 red
flashes.
Verify that the end device is online.
Not implemented.
Not implemented.
Not implemented.
Not implemented.
Not implemented.
Not implemented.
Refer to system errors table.
Troubleshooting