5.8 Placing RV on Elan Down ow
The Elan own ow is prepared in such a way that a Brink heat
recovery unit (HRV Type Renovent Elan can be placed on the
appliance.
When placing the Renovent Elan on an Elan own ow appli-
ance, it is assumed that the fronts of both appliances are kept
ush.
The connection "to dwelling" is connected at the top on the
Elan own ow appliance.
5.9 Filter connection top / bottom
If the return air duct must be connected on ( own ow version
or under (Up ow version the appliance, a lter unit must be
placed.
1
Open both lter doors of the appliance and remove the two
long countersunk Torx screws that hold the top panel.
2
Remove the top panel (it will be used later to replace the
lter mesh on the side of the appliance .

5.10 Cooling

An Elan appliance can be equipped for cooling. For that purpo-
se an Elan cooling block (cooling block water or cooling block
inverter must be installed in the air system and (if necessary
a condensing unit must be connected to the cooling block. In
addition, a relay (mounted in the interface cooling that comes
with the cooling block on the control unit must be connected to
the Elan on connection 7 and 8 on the 9-pole connector. (also
refer to §10.1 and §11.3 .
2 x
2 x
Torx T20
Torx T20
Elan 10 2.0 / Elan 16 2.0 / Elan 25 2.1
Use the optionally available coupling kit (Brink article code
007026 for Elan 10 Brink article code 008026 for Elan 16 25
that is placed between the Elan own ow appliance and the
Renovent Elan.
If a Renovent Excellent is placed separately in the installation
room, this coupling it is not necessary and the air supply con-
nection of the Renovent Excellent can be connected to the re-
turn duct of the Elan air heater.
3
Put the lter unit on the appliance and x it with the two
long Torx screws.
4
Replace the existing lter mesh by the panel that was ta-
ken out. For removing the lter mesh and mounting the top
panel, see §5.7.
When cooling is switched on, the system will always be running
at the air quantity cooling (setting step 4 . For switching on coo-
ling, a connection must be made between terminals 1 and 2 on
the 9-pole connector (also refer to §10.1 and §11.3 .
614391-F
filter
unit
13