Correction By Port Counts Of The Bc Controller - Mitsubishi Electric PQHY-P200YHM-A Data Book

Table of Contents

Advertisement

Heating
PQRY-P200YHM-A
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
60
Piping equivalent length (m)
PQRY-P250, 300YHM-A
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
60
Piping equivalent length (m)
(9)

Correction by port counts of the BC controller

Indoor unit sizes P200 and P250 must be connected to 2 ports on the BC controller.
Indoor unit sizes from P100 to P140 should normally be connected to 2 ports on the BC controller (set BC controller
DIP-SW 4-6 to its ON position).
In cases whereby indoor unit sizes from P100 to P140 are connected to only 1port on the BC controller (set BC controller
DIP-SW 4-6 to its OFF position), the cooling capacity of the indoor unit should be multiplied by a correction factor of 0.97.
80
100
120
140
160
180
80
100
120
140
160
180
PQRY-P400, 450, 500YSHM-A
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
60
Piping equivalent length (m)
PQRY-P550, 600YSHM-A
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
60
Piping equivalent length (m)
- 93 -
80
100 120 140
160
180
80
100
120
140
160
180