(16)-2 PQRY-P200-300YHM Piping

IF 16 ports or less are in use, i.e., if only one BC controller is in use with no sub BC controller

(Connection with standard CITY MULTI indoor units, PWFY-P100VM-E-BU, PWFY-P100/200VM-E-AU)

Note1. No Header usable on PQRY system.
Note2. Indoor unit sized P100-P250 should be connected to BC controller via Y shape joint CMY-R160-J1 ;
Note3. Indoor unit sized P100-P250 does NOT share BC controller ports with other Indoor units ;
Note4. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better ;
Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping length+"M" x Quantity of bent.
Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P100-P140 with 2 ports.
Note6. It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DIP-SW 4-6 to OFF).
However, the cooling capacity decreases a little (For details, refer to the chapter HEAT SOURCE UNITS,
WR2 SERIES, 3-(10) Correction by port counts of the BC controller).
Note7. Individual indoor units grouped together to connect to the BC controller via one port cannot operate
individually in heating and cooling modes at the same time. I.e., they must all function in either heating
Note8. Indoor capactiy is described as its model size. For example, PEFY-P63VMA-E, its capacity is P63.
Note9. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream.
For example, PEFY-P63VMA-E + PEFY-P32VMA-E : Total Indoor capacity = P63 + P32 = P95.
HU
H
H'
Reducer (P15~P50)
(attached with BC controller)
h1
Fig. 16-2A Piping scheme
Table
. Piping length limitation
16-2-1
Item
Total piping length
Farthest IU from HU
Distance between HU and BC
Farthest IU from BC controller
Heignt between HU and IU (HU above IU) H
Heignt between HU and IU (HU under IU) H'
Height between IU and BC
Height between IU and IU
HU : Heat source Unit ; IU : Indoor Unit ; BC : BC controller
*1. Refer to the section (16)-5.
*2. Details refer to Fig.16-2-1
*3. Farthest Indoor from BC controller "B+d" can exceed 40m till 60m if no Indoor sized P200, P250 connected. Details refer to Fig.16-2-1
*4. Distance of Indoor sized P200, P250 from BC must be less than 10m, if any.
Fig. 16-2-1 Piping length and height between IU and BC controller
70
60
50
40
30
20
10
0
0
Height difference between the main BC controller
and farthest indoor unit (m)
A
For heat source units equal to or larger than a size P400, on
the BC controller please ensure CMB-P
BC controller
Joint
a
(CMY-R160-J1)
IU
IU
(P15-P80)
(P100-250)
Piping in the figure
A+B+a+b+c+d
A+B+d
A
B+d
h1
h2
5
10
15
Fig. 16-2AA
V-GA1 is used.
Joint
(CMY-Y102S-G2)
B
b
c
IU
Max.3 sets for 1 port.
Total capacity <= P80
(m [ft.])
Max. length
Max. equivalent length
*1
165 [541']
190 [623']
110 [360'] *1
110 [360'] *1
40 [131'] *2*3
40 [131'] *3
50 [164']
40 [131']
15 [49'] (10 [32']) *4
15 [49'] (10 [32']) *4
Table
16-2-
3. Piping "A"size selection rule
Heat source Model Pipe(High pressure)
P200YHM
ø15.88 [5/8"]
P250YHM
ø19.05 [3/4"]
P300YHM
ø19.05 [3/4"]
Table
16-2-
4. Piping "B" size seleciton rule
Total down-stream Indoor capacity Pipe(Liquid)
P140 or less
Table
5. Piping "a", "b", "c", "d" size selection rule (mm [in.])
16-2-
Indoor Unit size
P15 to P50, GUF-50RD(H)
P63 to P140, GUF-100RD(H)
P200
P250
- 105 -
Joint CMY-R160-J1 Liquid side
CMY-R160-J1
Liquid
(
side)
(M)ø3/8"(Brazing)
M
BC controller
(M)ø3/8"(Brazing)
Joint CMY-R160-J1 Gas side
N
S
T
(S)ø5/8"(Brazing)
CMY-R160-J1
IU
Gas
(
side)
(S)ø5/8"(Brazing)
IU
d
h2
Table
2. Bent equivalent length "M"
16-2-
Heat source Model M (m/bent [ft./bent])
-
P200YHM
P250YHM
P300YHM
-
-
-
-
Pipe(Low pressure)
ø19.05 [3/4"]
ø22.20 [7/8"]
ø22.20 [7/8"]
Pipe(Gas)
ø9.52 [3/8"]
ø15.88 [5/8"]
Pipe(Lequid)
Pipe(Gas)
ø6.35 [1/4"]
ø12.70 [1/2"]
ø9.52 [3/8"]
ø15.88 [5/8"]
ø9.52 [3/8"]
ø19.05 [3/4"]
ø9.52 [3/8"]
ø22.20 [7/8"]
226
(N)ø9.52ID
226
(T)ø19.05ID
0.35 [1.15']
0.42 [1.38']
0.42 [1.38']
(mm [in.])
(mm [in.])

Advertisement