Table 10: Menu navigation
Menu
Submenu
Energy recovery
wheel (ERW)
Demand
ventilation
exhaust setup
Demand
ventilation
Demand
ventilation
exhaust service
Demand
ventilation
return fan setup
Demand
ventilation
return fan
service
Insert USB
USB functions
drive on the
controller for
data import and
export functions Restore from backup configuration
Advanced Graphic Touchscreen Display on 25 Ton to 80 Ton Johnson Controls Premier Rooftop Units
Parameters displayed
Heat recovery wheel status
Supply fan command
Econ free cooling available
Exhaust air heat recovery temp
Heat recovery wheel command
Heat recovery wheel output
Heat recovery FBD command
Exhaust type
Exhaust damper position for exhaust fan to turn
on
Exhaust damper position for exhaust fan to turn
Off
Building pressure setpoint
Exhaust fan manual bypass
Pickup gain
Exhaust fan status
Exhaust fan command
Building static pressure
Exhaust damper % command
Exhaust flow value
Power ex VFD
Exhaust fan VFD % command
Exhaust fan accumulated runtime
Exhaust fan VFD1 fault
Exhaust fan VFD2 fault
Exhaust air differential pressure
Exhaust fan motor control
Return fan installed
Return fan pressure high setpoint
Return fan pressure low setpoint
Building pressure setpoint
Exhaust fan manual bypass
Return fan diff flow setpoint
Exhaust flow value
Building static pressure
Return fan VFD percent command
Exhaust damper % command
Return fan command
Return air differential pressure
Operating return fan flow setpoint
Return fan motor control
Return fan VFD 1 fault
Return fan VFD 2 fault
Update status
Backup file name
Backup configuration
Johnson Controls
Conditions for parameter
displayed units and range
Off, max cooling, max heating, blocking
protection, heating control, heating low limit
Off, on
No, yes
°F
Off, on
%
Off, on
None, barometric, modulating damper, variable
frequency fan
% / 20–99
% / 10–89
iwg / -0.25 to 0.25
Off, on
0–100
Off-idle, on-normal command, off-disabled, off-
VFD fault, off-low building static pressure, off-
economizer damper position
Off, on
in w.c
%
cfm
Off, on
%
Hours
Normal, alarm
Normal, alarm
in w.c
Primary, redundant
False, true
in w.c (0-5)
in w.c (0-5)
in w.c (-0.25 to 0.25)
Off, on
in w.c (-0.25 to 0.25)
cfm
in w.c
%
%
Off, on
in w.c
cfm
Primary, redundant
Normal, alarm
Normal, alarm