Sun Microsystems Fire 15K Site Planning Manual
Sun Microsystems Fire 15K Site Planning Manual

Sun Microsystems Fire 15K Site Planning Manual

Hide thumbs Also See for Fire 15K:
Table of Contents

Advertisement

Quick Links

Sun Fire
15K/12K Systems
Site Planning Guide
Sun Microsystems, Inc.
www.sun.com
Part No. 806-3510-12
June 2003, Revision A
Submit comments about this document at: http://www.sun.com/hwdocs/feedback

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Fire 15K and is the answer not in the manual?

Questions and answers

Summary of Contents for Sun Microsystems Fire 15K

  • Page 1 Sun Fire 15K/12K Systems ™ Site Planning Guide Sun Microsystems, Inc. www.sun.com Part No. 806-3510-12 June 2003, Revision A Submit comments about this document at: http://www.sun.com/hwdocs/feedback...
  • Page 2 Copyright 2003 Sun Microsystems, Inc., 4150 Network Circle, Santa Clara, Californie 95054, Etats-Unis. Tous droits réservés. Sun Microsystems, Inc. a les droits de propriété intellectuels relatants à la technologie incorporée dans le produit qui est décrit dans ce document. En particulier, et sans la limitation, ces droits de propriété intellectuels peuvent inclure un ou plus des brevets américains énumérés à...
  • Page 3: Table Of Contents

    Contents Preface xi Physical Specifications 1–1 System Components 1–2 System Cabinet Physical Specifications 1–4 Raised Floor Installations 1–10 Non-Raised Floor Installation 1–10 Cabinet Floor Caster Weight Load 1–12 Planning Your Access Route 1–13 Environmental Requirements 2–1 Environmental Requirements 2–1 2.1.1 Suggested Ambient Temperatures 2–2 2.1.2 Suggested Ambient Relative Humidity 2–2...
  • Page 4 Network Planning 4–1 Network Connections 4–1 System Setup Information 4–2 Network Configurations 4–3 4.3.1 HA Network Configuration 4–4 4.3.2 Non-HA Network Configuration 4–5 System Setup Worksheets 4–6 4.4.1 Platform Name 4–6 4.4.2 Internal Networks 4–6 4.4.2.1 I1 Network 4–7 4.4.2.2 I2 Network 4–8 4.4.3 External Networks 4–8...
  • Page 5 Sun Fire 15K/12K Systems Cabinet Dimensions 1–8 FIGURE 1-4 Sun Fire 15K/12K Systems Cabinet Clearance Dimensions 1–9 FIGURE 1-5 Sun Fire 15K/12K Systems Floor Cutout and Base Dimensions Diagram 1–11 FIGURE 1-6 Sun Fire 15K/12K Systems Air Flow 2–5 FIGURE 2-1 Proposed Sun Fire 15K/12K Systems Configuration 2–7...
  • Page 6 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 7 Sun Fire 15K/12K Systems Load on Building Structure 1–12 TABLE 1-3 Environmental Requirements 2–1 TABLE 2-1 Sun Fire 15K/12K Systems Cabinet Power and Cooling Requirements 2–3 TABLE 2-2 System Power and Cooling Requirements Worksheet 2–4 TABLE 2-3 Facility Power Requirements 3–2 TABLE 3-1 Facility Power Cable Requirements Worksheet 3–2...
  • Page 8 viii Sun Fire 15K12K Systems Site Planning Guide • June 2003...
  • Page 9 Declaration of Conformity Compliance Model Number: 2080 Product Name: Sun Fire 15K/12K Systems European Union This equipment complies with the following requirements of the EMC Directive 89/336/EEC: EN55022:1995/CISPR22:1997 Class A EN55024:1998 EN61000-4-2 4 kV (Direct), 8 kV (Air) EN61000-4-3 3 V/m EN61000-4-4 1.0 kV Power Lines, 0.5 kV Signal Lines...
  • Page 10 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 11: Preface

    Chapter 1 provides suggested network configuration and worksheets for site- planning setups. Chapter 2 details the basic computer room layout and cooling requirements. Chapter 3 defines the facility power requirements for the Sun Fire 15K/12K systems. A power cable requirements worksheet and system power connections diagrams are included.
  • Page 12 You can view, print, or purchase a broad selection of Sun documentation, including localized versions, at: http://www.sun.com/documentation Contacting Sun Technical Support If you have technical questions about this product that are not answered in this document, go to: http://www.sun.com/service/contacting xii Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 13 You can submit your comments by going to: http://www.sun.com/hwdocs/feedback Please include the title and part number of your document with your feedback: Sun Fire 15K/12K Systems Site Planning Guide, part number 806-3510-12 United States Export Control Laws Notice Products covered by and information contained in this site planning guide are controlled by U.S.
  • Page 14 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 15: Physical Specifications

    C H A P T E R Physical Specifications Sun Fire 15K/12K systems come with various environmental requirements. Review the site preparation process flow diagram shown in as you begin to FIGURE 1-1 evaluate the needed requirements before your system installation.
  • Page 16: System Components

    Section 1.3, “Raised Floor Installations” on page 1-10). The Sun Fire 15K system cabinet has a concentrated load weight of 628.4 lb (285.6 kg) per three-inch caster (within the allowable load for a typical computer room raised floor that is generally made of steel construction). The Sun Fire 12K system cabinet has a concentrated load weight of 547.9 lb (249.0 kg).
  • Page 17 Sample configuration A - Top view Sample configuration B - Top view Sample configuration C - Top view Sun Fire 15K/12K Systems Cabinet Sample Configurations FIGURE 1-2 Chapter 1 Physical Specifications...
  • Page 18: System Cabinet Physical Specifications

    System Cabinet Physical Specifications lists the physical specifications for the Sun Fire 15K/12K systems. Use TABLE 1-1 to calculate the weight of your system as various components are added. TABLE 1-2 Physical Specifications for System Cabinets TABLE 1-1 Characteristic Sun Fire 15K System Cabinet...
  • Page 19: Table 1-2 System Weight By Components Worksheet

    System Weight by Components Worksheet TABLE 1-2 15K System 12K System Single Qty. Total Purch. Calculated Calculated System Component Qty. Weight Weight Qty. Actual Weight Actual Weight Base system cabinet (power module, power 785.0 lb 785.0 lb 785.0 lb 785.0 lb centerplane, fan backplane, cables, side (356.8 kg) (356.8 kg)
  • Page 20 (2.0 kg) _______ _______ Total weight shows the dimensions of the Sun Fire 15K/12K systems cabinet crate. FIGURE 1-3 shows the dimensions of the Sun Fire 15K/12K systems cabinet. FIGURE 1-4 Note – There might be slight variances in some component weights depending on customer configurations.
  • Page 21 12.0 in. 8.0 in. (30.5 cm) (20.3 cm) 32.0 in. 28.75 in. (81.3 cm) (73.0 cm) 48.0 in. 75.5 in. (191.8 (121.9 cm) Fork-lift side Pallet-jack side Sun Fire 15K/12K Systems Shipping Crate Dimensions FIGURE 1-3 Chapter 1 Physical Specifications...
  • Page 22 Note – The shipping pallet tie-down bracket holes in the front and rear of the lower chassis can also be used to hold-down or secure the system frame to the floor of your facility. Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 23 Sun Fire 15K/12K systems cabinet. FIGURE 1-5 For system cabinet electrical specifications and receptacle information, see TABLE 3-1 44.0 in (111.8 cm) 5.0 in. 5.0 in. Service clearance* (12.7 cm) (12.7 cm) Minimum distance required between 17.25 in.
  • Page 24: Raised Floor Installations

    FIGURE 1-6 the exact area required for your system. Ensure cabinets are positioned so all casters and leveling feet are on solid raised-floor tiles. Sun Microsystems™ suggests a minimum raised floor height of 24–36 in. (61.0– 91.5 cm). Non-Raised Floor Installation...
  • Page 25 Leveling feet diameter (4 places) 1.5 in. (3.8 cm) (also indicates location at top of cabinet for eye bolts) Sun Fire 15K/12K Systems Floor Cutout and Base Dimensions Diagram FIGURE 1-6 Note – In addition to the standard 4.0 in. X 8.0 in. (10.2 cm x 20.3 cm) floor cutout area (see dotted lines), any unused cable opening should be filled with a suitable material to block airflow.
  • Page 26: Cabinet Floor Caster Weight Load

    Sun Fire 15K/12K systems information on pounds per square foot on a building structure. Note – The Sun Fire 15K/12K systems require a shared-aisle space of 4.0 ft (121.9 cm). For the foot print weight, only unit dimensions and weight are calculated.
  • Page 27: Planning Your Access Route

    Note – There is a maximum cabinet threshold height of one inch with the kick plate installed and a maximum height of three inches after the kick plate has been removed (refer to the Sun Fire 15K/12K Systems Unpacking Guide for kick plate removal).
  • Page 28 1-14 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 29: Environmental Requirements

    TABLE 2-1 environmental requirements for the Sun Fire 15K/12K systems and the customer selected I/O expansion racks. If the system is significantly colder (40 °F [4 °C] or colder) than the environment in which you will install it, leave the system in its shipping crate at its final destination for 24 hours to prevent thermal shock and condensation.
  • Page 30: Suggested Ambient Temperatures

    Basic Cooling Requirements provide air conditioning information for the various TABLE 2-2 TABLE 2-3 components in the Sun Fire 15K/12K systems based upon the maximum system configuration. Use the worksheet in (see Appendix A for an expanded TABLE 2-3 form to use and retain for your records) to determine your system power and cooling requirements.
  • Page 31: Table 2-1 Environmental Requirements

    23,927 81,352 The dynamics of the Sun Fire 15K/12K systems power dissipation depends on the application and configuration. This manual accounts for these dynamics and is based on a rigorous code condition set that has been verified in a lab environment.
  • Page 32: Table 2-3 System Power And Cooling Requirements Worksheet

    _ x 94 x 3.4 = I/O adapters PCI (up to 72) _ x 24 x 3.4 = HDD (up to 36) _ x 40 x 3.4 = TOTAL ____ _____ Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 33 Cabinet front Cabinet rear (vented doors) (perforated doors) flow flow Air flow (raised floor) 62% front and rear Sun Fire 15K/12K system cabinet air flow ratios: 38% bottom Sun Fire 15K/12K Systems Air Flow FIGURE 2-1 Chapter 2 Environmental Requirements...
  • Page 34: Computer Room Layout

    The maximum cable distance between the Sun Fire 15K system and the I/O rack is 157.5 in. (400 cm). If you are using a single-ended SCSI device for this connection,...
  • Page 35 - Six (6) perforated tiles required Solid tile Perforated tile Proposed Sun Fire 15K/12K Systems Configuration FIGURE 2-2 Note – Casters and leveling feet, located at the corners of each cabinet, are to be positioned only on solid floor tiles. Chapter 2 Environmental Requirements...
  • Page 36 Proposed Sun Fire 15K/12K Systems—Multiple Configuration FIGURE 2-3 Note – The system power cables are 157.5 in. (400.1 cm) long. Consider the maximum distance to a power receptacle when positioning the system. Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 37: Facility And System Requirements

    To prevent catastrophic failures, the design of the power system must ensure that adequate power is provided to your Sun Fire 15K/12K systems. Sun Microsystems suggests that all power circuits supplying power to the Sun Fire 15K/12K systems be derived from dedicated electrical distribution panels. Electrical work and installations must comply with applicable local, state, or national electrical codes.
  • Page 38: Table 3-1 Facility Power Requirements

    ____ = ____ Total number of poles required * Contact a Sun Microsystems System Engineer for power cord quantity information when choosing the proper number of power cords needed for your system configuration. Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 39 Power source To Power source A To Power source B Front power supplies Rear power supplies Sun Fire 15K/12K Systems Power Connections—Redundant Power, Double FIGURE 3-1 Power Source (Power Source A and B) Chapter 3 Facility and System Requirements...
  • Page 40 System cabinet Power source A To power source A Front power supplies Rear power supplies Sun Fire 15K/12K Systems Power Connections—High-Reliability Power, FIGURE 3-2 Single Power Source (One Power Source) Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 41 Power source A To power source A Rear power supplies Front power supplies Sun Fire 15K/12K Systems Power Connections—Basic Single Power, Single FIGURE 3-3 Power Source (One Power Source, No Redundancy, Not Advisable) Chapter 3 Facility and System Requirements...
  • Page 42: Cabinet Grounding Requirements

    FIGURE 3-3 Cabinet Grounding Requirements The Sun Fire 15K/12K systems achieve earth ground through the power cords. For this reason, a gounding cable is not provided with the system. The power cords have three prongs: two for current and one for ground. At the AC input module, the ground prong, and system chassis are connected.
  • Page 43 1. Ensure the customer has properly grounded PDUs in the data center. The PDU must be earth ground. 2. Ensure all grounding points (raised floors and power receptacles) reference PDU ground. Note – The customer needs to procure the grounding cable. A grounding cable is not shipped with the system.
  • Page 44 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 45: Network Planning

    The Sun Fire 15K/12K systems require 10BASE-T or 100BASE-TX Ethernet connections for each System Control (SC) board. There are several networks to plan and set up for the Sun Fire 15K/12K systems. Two networks are internal to the platform, the others are external and require cabling.
  • Page 46: System Setup Information

    System Setup Information The information in the sections below must be determined prior to the installation of the Sun Fire 15K/12K systems. Most system information is network related and must be provided by the customer. identifies the network interfaces TABLE 4-2 available and their function.
  • Page 47: Network Configurations

    All external connections to the SC should be through the user community logical interface L–Cx, so clients are always directed to the main SC. Network Configurations For the System Controller, there are two types of network configurations: high availability (HA) and non HA. In either of the network configurations, the following is true: The domains can connect to any number of user communities.
  • Page 48: Ha Network Configuration

    Domain B DB-Cx SC0-I1 DC-I1 Domain C DC-Cx SC0-I2 SI2 Network SC1-I2 SC1-CA SC1-CA SC1-I1 DQ-I1 Domain Q DQ-Cx DR-I1 Domain R DR-Cx Spare SC Highly Available Network Configuration FIGURE 4-1 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 49: Non-Ha Network Configuration

    4.3.2 Non-HA Network Configuration A non-HA network configuration is shown in FIGURE 4-2 Advantages: Up to two user community connections to the System Controller. Disadvantages: A failure of any single network connection induces an SC failover. Community A F-CA Main SC DA-I1 Domain A DA-Cx...
  • Page 50: System Setup Worksheets

    4.4.1 Platform Name The Sun Fire 15K/12K systems require a platform name. The platform name, globally unique within the network, is a logical name given to an entire system and does not correspond to any host on the network. The platform name is used as the default prefix for host names of internal network interfaces, see Section 4.4.2,...
  • Page 51: I1 Network

    4.4.2.1 I1 Network Host names and IP addresses are required for the I1 network. For the System Controller, only one host name and IP address is assigned to the I1 network. Only the main SC actively connects to the I1 network. The host names and IP addresses can be automatically assigned by smsconfig(1M) during installation.
  • Page 52: I2 Network

    Each subnet must be unique within the network. The System Controller can connect to a maximum of two user communities. IP Networks Subnet Masks for External Networks Worksheet TABLE 4-7 User Community Network IP Network Subnet Mask Community A Community B Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 53: System Controller

    4.4.3.1 System Controller IP addresses are required for every interface on the System Controller that is cabled to a user community. The SC has two built-in Ethernet ports (labeled “Ethernet” and “Ext Ethernet”). Use the worksheet in to record this information. TABLE 4-8 Community Host Name IP Addresses for the System Controllers Worksheet TABLE 4-8...
  • Page 54: Domains

    Domain I (DI-Cx) Domain J (DJ-Cx) Domain K (DK-Cx) Domain L (DL-Cx) Domain M (DM-Cx) Domain N (DN-Cx) Domain O (DO-Cx) Domain P (DP-Cx) Domain Q (DQ-Cx) Domain R (DR-Cx) 4-10 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 55: Site Planning Checklists

    Microsystems training course, ES-421, Sun Fire 15K/12K Systems Server Administration? ❏ Is a security clearance required for this site? If so, has local Sun Microsystems Enterprise Services Management been notified of the required security level? Note: Clearances can take months to obtain, so timely notification is important.
  • Page 56: Environmental Requirements

    Are the floor cutouts for the system cabinet and each customer selected I/O expansion rack in place? ❏ Are suggested perforated floor panels in place? See Section 2.3, “Computer Room Layout” on page 2-6. Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 57: Network Planning

    ❏ Is the system positioned to correspond to the precise edge of raised-floor tile locations shown in the Sun Fire 15K/12K Systems Site Planning Guide? See Section 2.3, “Computer Room Layout” on page 2-6. Casters and leveling feet must be on solid raised-floor tiles.
  • Page 58: Installation Schedule

    Does each ramp incline in the access route, have an incline that is less than 10 degrees? Refer to the Sun Fire 15K/12K Systems Unpacking Guide. This is less than a 12-inch (30.5 cm) rise in ten feet (304.7 cm).
  • Page 59: Power And Cooling, And System Setup Worksheets

    Chapter 3 TABLE 3-2 “Facility Power Cable Requirements Worksheet” Chapter 4 TABLE 4-3 “Sun Fire 15K/12K Systems Platform Name Worksheet” TABLE 4-4 “IP Networks Subnet Masks for Internal Network Worksheet” TABLE 4-5 “Host Name IP Addresses for the I1 Network Worksheet”...
  • Page 60 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 61 System Weight by Components Worksheet Record Date ______________ 15K System 12K System Single Qty. Total Purch. Calculated Calculated System Component Qty. Weight Weight Qty. Actual Weight Actual Weight Base system cabinet (power module, 785.0 lb 785.0 lb 785.0 lb 785.0 lb power centerplane, fan backplane, cables, (356.8 kg) (356.8 kg)
  • Page 62 _______ (9 minimum for 12K system) I/O filler panel 4.5 lb 4.5 lb X ___ ________ ________ (9 minimum for 12K system) (2.0 kg) (2.0 kg) _______ _______ Total weight Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 63 System Power and Cooling Requirements Worksheet Record Date ______________ System Power Air Conditioning Components Qty. x Power Total (Watts) BTU/Hr System Cabinet Base system System Control (2) 2 x 182 x 3.4 = 1237.6 SC peripheral (2) 2 x 103 x 3.4 = 700.4 Fan trays (8)
  • Page 64 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 65 ____ Total number of poles required * Contact a Sun Microsystems System Engineer for power cord quantity information when choosing the proper number of power cords needed for your system configuration. Appendix A Power and Cooling, and System Setup Worksheets...
  • Page 66 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 67 Sun Fire 15K/12K Systems Platform Name Worksheet Record Date ______________ Platform Name Appendix A Power and Cooling, and System Setup Worksheets...
  • Page 68 A-10 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 69 IP Networks Subnet Masks for Internal Network Worksheet Record Date ______________ Network IP Network Subnet Mask 255.255.255.224 255.255.255.252 Appendix A Power and Cooling, and System Setup Worksheets A-11...
  • Page 70 A-12 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 71 Host Name IP Addresses for the I1 Network Worksheet Record Date ______________ I1 Network Interface Hostname IP Address System Control board (SC-I1) platform-sc-i1 Domain A (DA-I1) platform-a Domain B (DB-I1) platform-b Domain C (DC-I1) platform-c Domain D (DD-I1) platform-d Domain E (DE-I1) platform-e Domain F (DF-I1) platform-f...
  • Page 72 A-14 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 73 Host Name IP Addresses for the I2 Network Worksheet Record Date ______________ Interface Hostname IP Address SC0-I2 platform-sc0-i2 SC1-I2 platform-sc1-i2 Appendix A Power and Cooling, and System Setup Worksheets A-15...
  • Page 74 A-16 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 75 IP Networks Subnet Masks for External Networks Worksheet Record Date ______________ User Community Network IP Network Subnet Mask Community A Community B Appendix A Power and Cooling, and System Setup Worksheets A-17...
  • Page 76 A-18 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 77 Community Host Name IP Addresses for the System Controller Worksheet Record Date ______________ Cx Network Interface User Community IP Address System Controller 0, Ethernet System Controller 0, Ext Ethernet System Controller 1, Ethernet System Controller 1, Ext Ethernet Appendix A Power and Cooling, and System Setup Worksheets A-19...
  • Page 78 A-20 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 79 Host Name IP Addresses for the SC Logical Interface Worksheet Record Date ______________ SC0 Pathgroup SC1 Pathgroup User Community Logical Host Name Logical IP Address IP Address IP Address User Community A User Community B Appendix A Power and Cooling, and System Setup Worksheets A-21...
  • Page 80 A-22 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 81 Community Host Name IP Addresses for the Domain Worksheet Record Date ______________ Cx Network Interface User Community Hostname IP Address Domain A (DA-Cx) Domain B (DB-Cx) Domain C (DC-Cx) Domain D (DD-Cx) Domain E (DE-Cx) Domain F (DF-Cx) Domain G (DG-Cx) Domain H (DH-Cx) Domain I (DI-Cx) Domain J (DJ-Cx)
  • Page 82 A-24 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 83: Compliance Statements

    A P P E N D I X Compliance Statements...
  • Page 84 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 85 FCC radio frequency emission limits. Networking connections can be made using unshielded twisted-pair (UTP) cables. Modifications: Any modifications made to this device that are not approved by Sun Microsystems, Inc. may void the authority granted to the user by the FCC to operate this equipment.
  • Page 86 BSMI Class A Notice The following statement is applicable to products shipped to Taiwan and marked as Class A on the product compliance label. Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 87 Do not make mechanical or electrical modifications to the Follow all cautions and instructions marked on the equipment. Sun Microsystems is not responsible for equipment. regulatory compliance of a modified Sun product. Ensure that the voltage and frequency of your power source match the voltage and frequency inscribed on the equipment’s electrical rating label.
  • Page 88 Do not connect the power cord when the power supply has been removed from the system chassis. Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 89 Vergewissern Sie sich, daß Spannung und Frequenz Nehmen Sie keine mechanischen oder elektrischen Ihrer Stromquelle mit der Spannung und Frequenz Änderungen an den Geräten vor. Sun Microsystems, übereinstimmen, die auf dem Etikett mit den übernimmt bei einem Sun-Produkt, das geändert wurde, elektrischen Nennwerten des Geräts angegeben sind.
  • Page 90 Schließen Sie den Stecker des Netzkabels an eine in der Nähe befindliche, frei zugängliche, geerdete Netzsteckdose an. Schließen Sie das Netzkabel nicht an, wenn das Netzteil aus der Systemeinheit entfernt wurde. Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 91 Ne pas apporter de modification mécanique ou électrique une des ouvertures de l’appareil. Vous pourriez vous au matériel. Sun Microsystems n’est pas responsable de la trouver en présence de hautes tensions dangereuses. conformité réglementaire d’un produit Sun qui a été...
  • Page 92 Veillez donc à installer le produit à proximité d’une prise murale facilement accessible. Ne connectez pas la prise d’alimentation lorsque le châssis du système n’est plus alimenté. B-10 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 93 No realice modificaciones de tipo mecánico o eléctrico en el No introduzca nunca objetos de ningún tipo a través equipo. Sun Microsystems no se hace responsable del de los orificios del equipo. Pueden haber voltajes cumplimiento de las normativas de seguridad en los peligrosos.
  • Page 94 Laser KLasse 1 CD-ROM/DVD-ROM Precaución – El manejo de los controles, los ajustes o la ejecución de procedimientos distintos a los aquí especificados pueden exponer al usuario a radiaciones peligrosas. B-12 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 95 GOST-R Certification Mark Nordic Lithium Battery Cautions Norge ADVARSEL – Litiumbatteri — Eksplosjonsfare.Ved utskifting benyttes kun batteri som anbefalt av apparatfabrikanten. Brukt batteri returneres apparatleverandøren. Sverige VARNING – Explosionsfara vid felaktigt batteribyte. Använd samma batterityp eller en ekvivalent typ som rekommenderas av apparattillverkaren.
  • Page 96 B-14 Sun Fire 15K/12K Systems Site Planning Guide • June 2003...
  • Page 97 Index network, 4-1, 4-3 samples, 1-3 access requirement, 1-4 system diagram, proposed, 2-7 access route, 1-13 connection air conditioning requirements, 2-1 Ethernet, 4-1 air, intake, 2-1 network, 4-1 airflow direction, system (diagram), 2-5 cooling requirement, 2-3 altitude, 2-1 worksheet, 2-4 crate moving, 1-13 shipping, 1-13...
  • Page 98 I/O expansion racks, 1-2 redundant interface network, 4-2 double power source, 3-3 single power source, 3-4 requirements circuit breaker, 3-2 voltage, 3-2 load weight, floor, 1-2 single power source, 3-5 Index-2 Sun Fire 15K/12K Site Planning Guide • June 2003...
  • Page 99 power distribution unit, 3-6 preparing your site, 1-2 uninterruptible power system, 3-1 processor cabinet (single phase), power cable unpacking, 1-13 requirements worksheet, 3-2, A-7 upgrades, 2-3 raised floor voltage power requirements, 3-2 height, 1-10 installation, 1-10 requirements access route, 1-13 cooling, 2-3 weight, fully loaded system, 1-4 width...
  • Page 100 Index-4 Sun Fire 15K/12K Site Planning Guide • June 2003...

This manual is also suitable for:

Fire 12k

Table of Contents