IV.f – SERVICE MENU NAVIGATION (CONT):
Pressing the button next "SOLENOID" will cycle
refrigeration in the following order starting from the
OFF position:
REFRIGERATION TEST:
SOLENOID: OFF
SOLENOID: OFF
CABINET TEMP: 37F
COMP USAGE
Press Once: Maintenance compressor only
Press Twice: Maintenance compressor and Low Fan
(NOTE: Low Fan relay energizes High Speed on Blower(s))
Press Three Times: Maintenance compressor, Blast
Compressor, and High Fan
Press Four Times: Return to all OFF
Select "BACK" to return to the "SERVICE MENU" and
you may select "EXIT" from the "SERVICE MENU" to
return to the "MAIN MENU"
Selecting "COMP USAGE" will advance the display to
the "CLEANED CONDENSER COIL" screen.
REFRIGERATION TEST:
SOLENOID: OFF
CABINET TEMP: 37F
COMP USAGE
COMP USAGE
CLEAN CONDENSER COIL:
24 DAYS & 20 HRS
SINCE LAST CLEANING
CLEANED COIL
The "CLEAN CONDENSER COIL" screen gives a value
in hours and minutes of the maintenance compressors
run time.
This can be reset to 0 by selecting
"CLEANED COIL".
Select "BACK" to return to the
"REFRIGERATION TEST" menu.
f.2 – Probe Alarm Test (PROBES/ALARM)
Select "PROBES/ALARMS" from the "SERVICE
MENU" to access the product probe and audible
alarm test menu.
SERVICE MENU
REFR/AIR
DEF/COIL
PROBES/ALARM
PROBES/ALARM
PRINTER
IV. SMART CHILL CONTROL
BACK
BACK
BACK
EXIT
FAN
DISPLAY
IV.f – SERVICE MENU NAVIGATION (CONT):
PRODUCT PROBE TEMPS:
1 45 F
2 44 F
ALARM=OFF
Product probes 1,2,&3 will be displayed in real time. If
a probe is shorted - - - will be displayed next to the
probe number. If a product probe is open or dis-
connected nothing will be displayed next to the probe
number.
PRODUCT PROBE TEMPS:
1
2 44 F
ALARM=OFF
Pressing the button next to "ALARM=OFF" will activate
the audible alarm test.
"ALARM=ON" will deactivate the audible alarm test.
Select "BACK" to return to the "SERVICE MENU".
f.3 – Printer(s) Test (PRINTER)
Select "PRINTER" from the "SERVICE MENU" to
access the printer(s) test menu.
SERVICE MENU
REFR/AIR
PROBES/ALARM
PRINTER
PRINTER
PRINTER TEST:
RECORD: READY
LABEL: READY
Note: If no Label printer present "LABEL: READY" will not
be displayed
Pressing the button next to "RECORD READY" or
"LABEL READY" will run a test print for the printer
selected.
The test print will include a system
diagnostic as shown below.
SOFTWARE VERSION: 2.11
RUN CYCLES:
5 CYCLES
SINCE DEF:
5 CYCLES
MAXIMUM AIR: 78F
MINIMUM AIR:
0F
FAILURES:
PRINTER
YES
PROBE
NO
INTERRUPTED NO
CONTROL
NO
OVER TEMP
NO
SYSTEM FAIL
NO
DEFR. HEAT
YES
FLASH MEM.
NO
7
(Continued on next page)
44 F 3
BACK
- - - 3
BACK
Pressing the button next to
EXIT
DEF/COIL
FAN
DISPLAY
BACK