XIII. TROUBLE SHOOTING ( Continued)
CONDITIONS
CORROSION OCCURING ON
CONTROL BOARD
UNIT TRIPS A GROUND
FAULT BREAKER
RBC200 NOT HOLDING
TEMP IN "IDLE" MODE
RBC50 FOOD PROBE
HARNESS
RBC50 SMART CHILL
CONTROL
POSSIBLE SOLUTIONS
1. Use a "Food Grade" Silicone and with all power off to the unit,
spread a light coating of the silicone on all exposed connections.
2. Look for high humid conditions
1. Go to the relay box and with the power off to the unit pull all of
the wires off of terminal #1,and reinstall them one at a time. Once
you force the breaker to trip this will tell you which component
has failed
1. The temperature must be equal from top to bottom in cabinet.
2. The remote condenser will come on every other cycle on Control
Versions 1.12 and later.
1. Should the "Food Probes" fail to read any temperature you will
need to check them for breaks in the wires or separation of the
insulation.
2. Look at the "Sockets" in the ceiling of the box were the Food
Probes plug into for any broken pieces.
3. Pull the Socket Plate down to inspect the top of the sockets for
broken wires or corrosion.
4. Should the Harness be bad it will have to be replaced.
5. To replace the Harness you will have to replace to complete top
due to the harness being foamed into the top at the time of
manufacture.
6. You will have to pull the Control Panel and disconnect the Food
Probe Harness in the back ductwork.
7. Remove the Stainless Steel Work top.
8. Remove the top that contains the Food Probe Harness and install
the new one in its place.
9. Reinstall all of the parts to normal working positions.
1. On the RBC50 it has been found that the "Defrost Time" setting
can possibly be set to 40 min.
2. Should this be true of the unit you are working on, you will need to
go into program "85" and navigate thru the settings to press the
"Reset" button in the first screen and then go thru until you get to
the "Security" screen.
3. Press the "Reset" button again.
4. All settings will default to original settings (RBC100). Use the
button to the right of "Machine Size" to change from the 100 to
the 50 and then press "Exit".
5. In the next screen press the "Yes" button to save your changes.
6. Proceed to the Main Menu.
7. Go back into the "85" program and press the rest button for the
second time. Then go to the screen that shows the defrost time.
8. Use the down arrow to change the defrost button to 15 min.
9. Press the "Back button to go back to the first screen in program
"85" to enter the correct serial number this allows usage of the
Blast Chill Communication software.