Contemporary Controls BASstat BAST-421C-B2 User Manual page 23

Bacnet communicating thermostat for modulating fan coil operation
Table of Contents

Advertisement

Object name
Current
Temperature
Active Temperature
Setpoint
Built-in
Temperature
Sensor
Remote
Temperature
Sensor
Current Humidity
Current Dew Point
Current CO
2
Reading
Control Valve
Feedback
Modulating/
Floating Output 1
Modulating/
Floating Output 2
Modulating Fan
Output
Control Output
Percentage
Voltage Input Value
AI 1
Percentage
2 nd Remote
Temperature
3rd Remote
AI 15
Temperature
Cooling Temperature
Setpoint
Temperature
Override
Timer Off
Heating
Temperature
Setpoint
UM-15093000-AA1
Type &
Readable/
Instance
Writable
AI 0
R
AI 1
R
AI 2
R
AI 3
R
AI 4
R
AI 5
R
AI 6
R
AI 7
R
AI 8
R
AI 9
R
AI 10
R
AI 11
R
AI 12
R
AI 13
R
AI 14
R
R
AV 0
R/W
AV 1
R/W
AV 2
R/W
AV 3
R/W
Description
Current Temperature
Active Temperature Set-
Point
Built-in Temperature
Sensor Reading
Remote Temperature
Sensor Reading
Current Humidity
Current Dew Point
Current CO
Reading
2
Control Valve Feedback
Modulating/ Floating Output
1 (Cooling)
Modulating/ Floating Output
2 (Heating)
Modulating Fan Output
CO2 Control Output
Percentage
Voltage Input Value
Analog Input 1 Percentage
Value
2
remote temperature
nd
Value
3rd Remote Temperature
Sensor Reading Value
Cooling Temperature Set
Point
Assigned Current
Temperature
Timer Off (Only for Models
with Countdown Timer
Heating Temperature Set
Point
Range and Definition
-999~9999: -99.9~999.9
℃/°F
°C :0~500 (0.0~50.0℃)
°F : 320~1220
(32.0~122.0°F)
-999~9999:-99.9~999.9
℃/°F
-999~9999:-99.9~999.9
℃/°F
0~1000: 0.0~100.0%RH
-999~9999: -99.9~999.9
°C/°F
0~3000: 0~3000 ppm
0~1000 (0.0%~100.0%)
0~100: 0~100 %
0~100: 0~100 %
0~100: 0~100 %
0~100: 0~100 %
0~150 (0.0~15.0 VDC)
0~1000 (0.0%~100.0%)
-999~9999:-99.9~999.9℃
/°F
-999~9999:-99.9~999.9℃
/°F
°C :0~500 (0.0~50.0℃)
°F: 320~1220
(32.0~122.0°F)
-999~9999
(-99.9~999.9℃/°F)
0~24: 0~24 Hours Count
Down
℃/°F
-999~9999: -99.9~999.9
Page 22