Download Print this page

Advertisement

Quick Links

1. Install the potentiometer module(1) in
the designed section of the unit as
shown. Tighten the screw that secures
the pot arm and spring.
The pot gearwheel should be aligned
and secured to the larger gearwheel(2).
2. Install the 4-20mA transmitter module(3)
into the designed position and tighten the
respective screws.
3. When used for the 4-20mA feedback, secure
the potentiometer connector(4) to the
transmitter (3).
NOTE: Make sure V200E/P has first been properly calibrated!
1. Power up the current loop.
2. Connect a low ohmic ampere meter over the test points(5).
3. Set the valve/actuator to 4mA or the zero
position.
4. Turn the feedback potentiometer shaft(6) with
a screw driver until you read 3.5 - 4.5 mA on the meter.
5. Adjust the trim potentiometer(7) marked zero
so that the meter reads 4mA.
6. Increase the input signal to a full
20mA or 100%.
7. Adjust the trim potentiometer(8) marked
span until the meter reads 20mA.
8. Re-check the zero position (4mA) and
make fine adjustments if necessary.
A very basic calibration can be accomplished
without a meter, using the two LED's.
Red LED lights up at 4mA, Green LED lights up at 20mA.
V200 4/20mA Installation
V200 4/20mA Calibration
www.vac.se - www.vacaccessories.com
2
2
5
7
8
4
3
CCV
1
4
3
1
6
Pot adjustment.eps
6
5
6
Power Supply: 7-30VDC
Load max 850 Ohms @ 24 VDC
92125r3 4-20mA Installation
1

Advertisement

loading

Summary of Contents for VAC V200

  • Page 1 V200 4/20mA Installation 1. Install the potentiometer module(1) in the designed section of the unit as shown. Tighten the screw that secures the pot arm and spring. The pot gearwheel should be aligned and secured to the larger gearwheel(2). 2. Install the 4-20mA transmitter module(3) into the designed position and tighten the respective screws.
  • Page 2 Turn back til 13.0-14.0mA 4. Adjust the ZERO-pot counter clockwise to 4mA. 5. Open the valve. 6. Adjust the SPAN-pot(3) clockwise to 20mA. 7. Close the valve. 8. Repeat (steps 4-7) until the unit is properly set. www.vac.se - www.vacaccessories.com 92125r3 4-20mA Installation...

This manual is also suitable for:

V200eV200p