Heat source parameter group
"Coolant buff. cyl."
"Cool.circ.pump NC"
Parameter
Adv.rntime
Run-on time
Start delay
Anti-blocking prot.
Weekday
■
Time
■
Dur.
■
Set val. low t.maint
Frost prot.
Spread
Ctrllr P-factor
Ctrllr I-factor
Ctrllr D-factor
"Cooling curve"
Two cooling curves can be set here for charging the
coolant buffer cylinder subject to the outside tempera-
ture:
"Day/night changeover cooling curve"
Parameter
Operat.
Start day
End day
30
(cont.)
Factory
Min.
setting
60 s
30 s
30 s
10 s
30 s
0 s
We
Mo
09:00
2 min
1 min
5 °C
5 °C
3 °C
0 °C
5 K
3 K
5
0.001
0
Factory setting
07:00 h
22:00 h
Max.
Description
120 s
Advance runtime for circulation pump
60 s
Run-on time for circulation pump
120 s
Start delay for circulation pump
See page 63.
Su
10 min
30 °C
Low end set value for circulation pump
10 °C
Frost protection temperature for circulation pump
10 K
Set value for spread with controlled circulation
pump
P-factor for controlling the circulation pump for
spread or low temperature maintenance
I-factor for controlling the circulation pump for
spread or low temperature maintenance
D-factor for controlling the circulation pump for
spread or low temperature maintenance
Day curve (for time period, see "Day/night change-
■
over cooling curve")
■
Night curve
See also page 63.
Description
Status (day (On) / night (Off))
Time of changeover from night curve to day
curve
Time of changeover from day curve to night
curve