Inspection item
5.1.4
Checking the inverter and converter modules
Preparation
• Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W). (The cables between the
inverter and the converter unit, between the inverters, and between the converter units does not need to be removed.)
• Prepare a tester. (For the resistance measurement, use the 100 range.)
Checking method
Change the polarity of the tester alternately at the inverter terminals R/L1, S/L2, T/L3, U, V, W, P/+, and N/- and check the
electric continuity.
NOTE
• Before measurement, check that the smoothing capacitor is discharged.
• At the time of electric discontinuity, the measured value is almost ∞. When there is an instantaneous electric continuity, due to
the smoothing capacitor, the tester may not indicate ∞. At the time of electric continuity, the measured value is several to
several tens of . If all measured values are almost the same, although these values are not constant depending on the
module type and tester type, the modules are without fault.
Module device numbers and terminals to be checked
Converter module
D1
D2
D3
R/L1
C
S/L2
T/L3
D4
D5
D6
Tester
polarity
R/L1,
P/+
D1
P/+
R/L1,
S/L2,
P/+
D2
P/+
S/L2,
T/L3
P/+
D3
P/+
T/L3
U
P/+
TR1
P/+
U
V
P/+
TR3
P/+
V
W
P/+
TR5
P/+
W
(Assumes the use of an analog meter.)
90
PRECAUTIONS FOR MAINTENANCE AND INSPECTION
Inverter module
P/+
P/+
TR1
C
TR4
N/-
N/-
Tester
polarity
Result
Discontinuity
R/L1,
D4
Continuity
N/-
R/L1, Discontinuity
Discontinuity
S/L2,
D5
Continuity
N/-
S/L2, Discontinuity
Discontinuity
T/L3
D6
Continuity
N/-
T/L3 Discontinuity
Discontinuity
U
TR4
Continuity
N/-
Discontinuity
V
TR6
Continuity
N/-
Discontinuity
W
TR2
Continuity
N/-
TR3
TR5
U
V
W
TR6
TR2
Result
N/-
Continuity
N/-
Continuity
N/-
Continuity
N/-
Continuity
U
Discontinuity
N/-
Continuity
V
Discontinuity
N/-
Continuity
W
Discontinuity