CLEARING FAULT HISTORY

To clear the fault history, use the step chart below.
Step
1
Power on the VFD.
2
Press the ESC button 4 times or until the screen displays b001.
3
Use the arrow buttons to navigate to parameter b084.
Press the SET button to enter the parameter, use the UP arrow to set the value to 01 and press the SET button to save
4
the change.
5
Use the UP arrow to navigate to parameter b180.
Press the SET button to enter the parameter, use the UP arrow to set the value to 01 and press the SET button to save
6
the change and the clearing process will begin. Once the process is complete the screen will return to d001.
7
You can use press and hold the ESC button until the screen returns to the frequency monitor or just cycle power.