Electric Characteristics

11. Electric Characteristics
Indoor Unit
Outdoor Unit
FTXS09LVJU
RXS09LVJU
FTXS12LVJU
RXS12LVJU
FTXS15LVJU
RXS15LVJU
FTXS18LVJU
RXS18LVJU
FTXS24LVJU
RXS24LVJU
FDXS09LVJU
RXS09LVJU
FDXS12LVJU
RXS12LVJU
Symbols:
MCA
: Min. circuit amps (A)
MOP
: Max. overcurrent protection (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated load amps (A)
OFM
: Outdoor fan motor
IFM
: Indoor fan motor
W
: Fan motor rated output (W)
FLA
: Full load amps (A)
52
Power Supply
Hz - Volts
Voltage Range
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
60 - 230
COMP
MCA
MOP
RHz
RLA
3.2
8.00
15
46
2.9
4.4
8.75
15
68
3.9
4.7
13.75
20
50
4.2
6.6
13.75
20
65
5.9
7.9
17.50
20
42.6
7.1
4.1
8.00
15
57
3.7
5.9
8.75
15
82
5.3
Note:
1. RLA is based on the following conditions.
Indoor temp. 80°FDB / 67°FDB (26.7°CDB / 19.4°CDB)
Outdoor temp. 95°FDB (35°CDB)
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of a fuse, use a circuit breaker.
5. Be sure to install a Ground Fault Circuit Interrupter / Earth Leakage
Circuit Breaker that can handle higher harmonics because this unit
uses an inverter, and therefore must be capable of handling high
harmonics in order to prevent malfunction.
Split Type Air Conditioners FTXS-L / FDXS-L Series
EDUS091128
OFM
IFM
W
FLA
W
FLA
23
0.22
23
0.15
23
0.22
23
0.15
53
0.32
48
0.31
53
0.32
48
0.32
66
0.40
48
0.57
23
0.22
62
0.52
23
0.22
62
0.52