Electric Characteristics - Daikin Super Multi NX 3MXS-G Series Engineering Data

Table of Contents

Advertisement

Electric Characteristics

11. Electric Characteristics
Outdoor Unit
2MXS18GVJU
3MXS24JVJU
4MXS32GVJU
Symbols:
MCA
: Min. circuit amps (A)
MOP
: Max. overcurrent protection (A)
MSC
: Max. current during starting compressor (A)
RLA
: Rated load amps (A)
OFM
: Outdoor fan motor
W
: Fan motor rated output (W)
FLA
: Full load amps (A)
218
Power Supply
Hz
Volts
Min.
208
187
60
230
207
208
187
60
230
207
208
187
60
230
207
Max.
MCA
MOP
229
11.1
20
253
229
17.8
20
253
229
18.0
20
253
Note:
1. RLA is based on the following conditions.
Cooling
Indoor temp.: 80°FDB (27°CDB) / 67°FWB (19°CWB)
Outdoor temp.: 95°FDB (35°CDB)
2. Voltage range:
Units are suitable for use on electrical systems where voltage
supplied to unit terminal is not below or above listed range limits.
3. Maximum allowable voltage variation between phases is 2%.
4. MCA represents maximum input current.
MOP represents capacity which may accept MCA.
5. Select wire size based on the large value of MCA.
6. MOP is used to select the circuit breaker and the ground fault
circuit interrupter.
7. Be sure to install a ground leakage detector that can handle
higher harmonics. This unit uses an inverter, so it requires a
ground leakage detector capable of handling high harmonics in
order to prevent malfunctioning of the ground leakage detector .
SUPER MULTI NX 2/3/4MXS-G/J Series Heat Pump
EDUS121131
Comp.
OFM
MSC
RLA
W
9.1
8.5
53
8.3
7.7
13.3
11.7
66
12.0
10.4
15.3
13.6
66
13.8
12.1
FLA
0.26
1.02
1.02
3D059055A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents