■Outline drawings

■Attention
1. When using the product where it is exposed to high temperatures and humidity (40℃ or more, RH 80% or more), or where
fog occurs frequently, moisture is likely to condense in the core, and may result in condensation build up in the unit. The
product should not be used under such conditions.
2. Outdoor air may enter the Lossnay owing to the pressure difference between indoor and outdoor or external winds even
when the product is not operated. It is recommended to install an electrically operated damper to block the outdoor air.
3. In a cold weather area, an area with strong external winds or where fog occurs frequently, cold outdoor air, external winds
or fog may be introduced into the product when its operation is stopped. It is recommended to install an electrically operated
damper.
4. In a cold weather area, or others, dewing or freezing could occur on the main unit, where the duct is connected, or other
sections, depending on the conditions of outdoor air and indoor temperature and moisture, even if they are within the range
of operating conditions. Make sure to check the operating conditions and other precautions, and do not use the product if
dewing or freezing is anticipated.
5. The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor louvers from the Lossnay, and
properly insulated. (The entry of rain water may cause power leakage, fire, or damage to household property.)
6. The two outdoor ducts must be covered with heat-insulating material in order to prevent condensation from forming. If it is
expected that the ambient temperature around the place where the Lossnay unit is installed will be high during the summer
air conditioning season, it is recommended that the indoor ductwork should be covered with insulation material.
7. Inspection opening (450×450mm or more) must be installed on the filter and Lossnay core removal side.
8. Before starting installation, be sure to fix ceiling suspension fixture with the attached screws according to the installation
manual.
OUTLINE DRAWINGS
DATE
TYPE
22-Sep-2014
MODEL
NUMBER
※Specification may be subject to change without notice.
CEILING RECESSED LOSSNAY
LGH-100RVX-E
N14HHGU0033A
UNIT
SCALE
mm
N.T.S
2/5