MODEL
Heat exchange system
Heat exchanger material
Cladding
Heat insulation material
Motor
Blower
Filter
Surrounding air condition
Suction air condition
Supply fan operation under
low outdoor temperature
Function
Weight
Electrical power supply
Ventilation mode
Fan speed
Running current
[A]
Input power
[W]
3
Air volume
[m
/h]
[L/s]
External static pressure [Pa]
Exchange Temperature
efficiency
Enthalpy Heating
[%]
Cooling
Noise
[dB]
Insulation resistance
Direct strength
■Characteristic curve
350
300
250
200
150
100
50
0
0
0
■Attention
1. The running current, the input power, the efficiency and the noise are based on the rating air volume, and
230V/50Hz. The noise is measured at 1.5m under the center of the unit in an anechoic chamber.
2. Temperature exchange efficiency (%) is based on winter condition.
3. Heat recovery ventilation mode starts automatically while detecting OA temperature lower than 8℃, even Bypass
mode is selected. Remote controller continues to display "Bypass ventilation" in this case.
4. Mitsubishi Electric measures figures in the chart according to Japan Industrial Standard (JIS B 8628), therefore the
characteristic curves are measured by chamber method.
5. The noise level at 1.5m away from outlets in the 45°direction is about 21dB greater than the indicated value at
fanspeed4.
6. On-site measurements by pitot tube method could be as much 20% difference from JIS test room conditions. If the
measuring point is close to sources of turbulence like bends, contractions and dampers etc., it is difficult to measure
air volume correctly. A straight duct length more than 10D (D=duct diameter) from the source of turbulence is
recommended for correct measurement. On-site measurement should therefore be measured in accordance with
BSRIA guideline (Commissioning Air Systems. Application procedures for buildings AG3/89.3(2001)).
7. Use this unit between static pressure 60Pa and 240Pa at Fan speed4. Otherwise the motor protection may work
and reduce its output or the noise level might be larger.
SPECIFICATIONS
LGH-100RVX-E
Heat recovery ventilating system
Special treated paper plate heat exchanger
Galvanized steel sheet
Self-extinguishing urethane foam
DC motor
245mm diameter centrifugal fan
Non-woven fabrics filter (Gravitational method 82% EU-G3)
Shall be between -10 ℃ and 40 ℃ , 80%RH or less
Shall be lower than 40 ℃ , 80%RH
-10 ℃ to -15 ℃ : Intermittent operation 60 min ON, 10 min OFF.
-15 ℃ or less : Intermittent operation 55 min OFF, 5 min ON.
Heat recovery ventilation/ Bypass ventilation, Fan speed 1,2,3,4
54kg
220-240V/50Hz, 220V/60Hz
Heat recovery mode
SP4
SP3
2.50
1.20
420
200
1000
750
278
208
170
96
80.0
83.0
72.5
74.0
71.0
73.0
37.0
31.0
10M Ω or more
AC 1500V 1 minute
SP3
SP2
SP1
500
50
100
150
200
Air volume
DATE
22-Sep-2014
SP2
SP1
SP4
0.50
0.17
2.50
75
21
420
500
250
1000
139
69
278
43
11
170
86.5
89.5
-
78.0
87.0
-
77.0
85.5
-
23.0
18.0
38.0
250㎜ dia straight pipe length
SP4
1000
250
300
350
※Specification may be subject to change without notice.
TYPE
CEILING RECESSED LOSSNAY
MODEL
LGH-100RVX-E
N14HHGU0033A
NUMBER
SIGN
Bypass mode
SP3
SP2
1.20
0.51
200
75
750
500
208
139
96
43
-
-
-
-
-
-
32.0
24.0
90
100m
80
80m
70
60
60m
50
40m
40
30
20
1500
3
(m
/h)
(L/s)
400
SP1
0.19
23
250
69
11
-
-
-
18.0
1/5

Advertisement

loading

Summary of Contents for Mitsubishi Electric LGH-100RVX-E

  • Page 1 3. Heat recovery ventilation mode starts automatically while detecting OA temperature lower than 8℃, even Bypass mode is selected. Remote controller continues to display "Bypass ventilation" in this case. 4. Mitsubishi Electric measures figures in the chart according to Japan Industrial Standard (JIS B 8628), therefore the characteristic curves are measured by chamber method.
  • Page 2: Outline Drawings

    8. Before starting installation, be sure to fix ceiling suspension fixture with the attached screws according to the installation manual. ※Specification may be subject to change without notice. DATE TYPE CEILING RECESSED LOSSNAY OUTLINE DRAWINGS 22-Sep-2014 MODEL LGH-100RVX-E N14HHGU0033A NUMBER...
  • Page 3: Wiring Diagrams

    4. Wiring work must be performed by qualified professionals. 5. All supply circuits must be disconnected before obtaining access to the terminal devices. ※Specification may be subject to change without notice. DATE TYPE CEILING RECESSED LOSSNAY WIRING DIAGRAMS 22-Sep-2014 MODEL LGH-100RVX-E N14HHGU0033A NUMBER...
  • Page 4: Safty Notes

    Lossnay unit, make sure to install safety equipment for the external devices. (It could cause fire, damage, etc. without safety equipment) ※Specification may be subject to change without notice. DATE TYPE CEILING RECESSED LOSSNAY SAFTY NOTES 22-Sep-2014 MODEL LGH-100RVX-E N14HHGU0033A NUMBER...
  • Page 5 Air Filters : Around 5 years with maintenance at stated periods High efficiency filters : 3000 hours Motor : 30000 hours ※Specification may be subject to change without notice. DATE TYPE CEILING RECESSED LOSSNAY SAFTY NOTES 22-Sep-2014 MODEL LGH-100RVX-E N14HHGU0033A NUMBER...
  • Page 6 Related Links Model Number: LGH-100RVX-E LGH-100RVX-E Specification (N14HHGU0033A) LGH-15-200RVX-E Declaration of Conformity LGH-15-200RVX-E Installation Manual (875HK9602) LGH-15-200RVX-E Instruction Book (875HK9501) LGH-15-200RVX-E Service Manual (U204-A) LGH-15-200RVX-E Technical Manual (Y14-003 Jan.2015) LGH-15-200RVX-E Technical Manual Control (Y14-003 Jan.2015) Lossnay RVX Series Brochure Lossnay Weatherproof Housing LGH-80-100 RVX...