3.2 Pulse input setting

Refer to page C-20
3.3 Filter maintenance and fan power up setting against lter choking
Set the schedule for lter cleaning based on the estimated concentration of dust in the air.
When fan power up is available, exhaust and supply fans power up at 1,000 hours and 2,000 hours gradually .
If function
or
No.55
No.56
Estimated hour differs by actual operated fan speed.
DIP-SW
Setting
check
SW No.
Setting
-
-
SW5-5
OFF
(Factory setting)
ON
<Caution>
controller or the Lossnay remote controller.
After cleaning the lter, the lter cleaning icon can be reset. Refer to the Instruction book for the remote controller.
3.4 Lossnay core maintenance indicator setting
Set to enable Lossnay core maintenance indicator. Estimated hour differs by actual operated fan speed.
This function is N/A from Lossnay unit DIP-SW.
Estimated hour differs by actual operated fan speed.
DIP-SW
Setting
check
SW No.
Setting
-
N/A
-
3.5 Automatic recovery setting after power interruption
Set for automatic recovery following power interruption.
DIP-SW
Setting
check
SW No.
Setting
-
OFF
SW5-4
(Factory setting)
-
ON
is already worked, fan power up function may not be available.
PZ-61DR-E
Function
Setting
No.
Data
0
-
(Factory
setting)
-
1
1
2
3
PZ-61DR-E
Function
Setting
No.
Data
0
-
(Factory
2
setting)
-
1
PZ-61DR-E
Function
Setting
No.
Data
0
-
(Factory
setting)
5
1
-
2
3
Function / 3. Function setting contents
CHAPTER 2
Filter
Setting
maintenance
check
indicator
DIP-SW priority
Indicate at
estimated 3,000 hrs
N/A
Indicate at
estimated 3,000 hrs
Setting
Lossnay core maintenance
check
indicator
N/A
Indicate at estimated 6,000 hrs
Setting
Automatic recovery
check
DIP-SW priority
Stop when the power is on
Start when the power is on
Lossnay returns to the state before interruption
Fan power
UP
N/A
N/A
Available
C-31