Function / 4. Fan speed control
CHAPTER 2
4.2.6 Supply fan power up setting / Exhaust fan power up setting
Use these functions when the air volume needs to be increased after installation.
Function
is for supply fan power up and function
No.55
When function
No.1
is ON and fan speed already reached the maximum power, this function is N/A.
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
-
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
-
4.2.7 Fan speed for air volume "High" input
Set the fan speed setting when receiving "High" signal from remote controllers (e.g. remote controller of City Multi and Mr. Slim,
PZ-43SMF-E) that have High/Low or High/Middle/Low air volume.
DIP-SW
Setting
check
SW No.
Setting
-
SW2-9
OFF
(Factory setting)
ON
<Caution>
4.2.8 Fan speed for air volume "Low" input
Set the fan speed setting when receiving "Low" signal from remote controllers (e.g. remote controller of City Multi and Mr. Slim,
PZ-43SMF-E) that have High/Low.
DIP-SW
Setting
check
SW No.
Setting
-
SW2-10
OFF
(Factory setting)
ON
<Caution>
4.2.9 External fan speed input setting (0-10VDC)
Refer to page C-54
C-40
PZ-61DR-E
Function
Setting
No.
Data
0
-
(Factory
setting)
-
1
55
-
2
-
3
-
4
PZ-61DR-E
Function
Setting
No.
Data
0
-
(Factory
setting)
-
1
56
-
2
-
3
-
4
PZ-61DR-E
Function
Setting
No.
Data
0
-
(Factory
setting)
61
1
2
PZ-61DR-E
Function
Setting
No.
Data
0
-
(Factory
setting)
62
1
2
is for exhaust fan power up.
No.56
Setting
Supply fan power up
check
N/A
1 level up
2 level up
3 level up
4 level up
Setting
Exhaust fan power up
check
N/A
1 level up
2 level up
3 level up
4 level up
Setting
Operating fan speed
check
DIP-SW priority
Fan speed 4
Fan speed 3
Setting
Operating fan speed
check
DIP-SW priority
Fan speed 2
Fan speed 1