6.2 How to set Night-purge from the remote controller (PZ-61DR-E)
<STEP 1> Night-purge setting 1) Air volume
Set fan speed during Night-purge.
When setting data is "0" , Night-purge
function is not available.
This function is N/A from Lossnay unit
DIP-SW.
<STEP 2> Night-purge setting 2) Outdoor and indoor temperature difference
Set one of the conditions for Night-purge
start, temperature difference between
indoor and outdoor.
When the actual difference bet ween
indoor
and outdoor becomes bigger than the
setting, Night-purge starts.
This function is N/A from Lossnay unit
DIP-SW.
<STEP 3> Night-purge setting 3) Threshold of outdoor temperature
Set one of the conditions for Night-purge
start, maximum outdoor temperature
within 24 hours.
When this setting temperature is low,
it is likely to start Night-purge.
This function is N/A from Lossnay unit
DIP-SW.
<STEP 4> Night-purge schedule setting
Set the "Night-purge schedule" after "Off schedule" like the example on the right (upper).
Off setting is necessary before Night-purge setting.
If not, Night-purge does not start.
For example, the setting as shown on the right (lower) is NOT correct.
set in the weekly timer.
*If there is no schedule after a Night-purge, Lossnay will stop after 24 hours of Night-purge
operation.
Note;
How to set Night-purge from the centralized controller (AE-200E, ver. 7.30 or later), refer to the manual of the centralized
controller.
CHAPTER 2
DIP-SW
Setting
check
SW No. Setting
-
-
-
-
N/A
-
-
-
-
-
-
DIP-SW
Setting
check
SW No. Setting
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
DIP-SW
Setting
check
SW No. Setting
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Function / 6. Night-purge function
PZ-61DR-E
Function No. Setting Data
0
(Factory setting)
1
30
2
3
4
PZ-61DR-E
Function No. Setting Data
0
1
2
3
31
4
5
(Factory setting)
6
7
PZ-61DR-E
Function No. Setting Data
0
1
2
(Factory setting)
3
4
5
6
7
32
8
9
10
11
12
13
14
15
Setting
Air volume
check
N/A (Night-purge
function is not available)
Fan speed 1
Fan speed 2
Fan speed 3
Fan speed 4
Setting
Indoor temperature -
check
outdoor temperature
Setting
Threshold of outdoor
check
temperature
15 ˚C or more
16 ˚C or more
17 ˚C or more
18 ˚C or more
19 ˚C or more
20 ˚C or more
21 ˚C or more
22 ˚C or more
23 ˚C or more
24 ˚C or more
25 ˚C or more
26 ˚C or more
27 ˚C or more
28 ˚C or more
29 ˚C or more
30 ˚C or more
OK
NG
C-47