Telguard TG-7FP Installation & Operation Manual

Telguard TG-7FP Installation & Operation Manual

Sole path communicator
Hide thumbs Also See for TG-7FP:
Table of Contents

Advertisement

Quick Links

TG-7FP
Inst allat io n & Op erat io n Guid e
COMPANY CONFIDENTIAL
Fo r use b y TELGUARD c usto mers o nly.
Distrib utio n to o ther parties stric tly pro hib ited.
No vember 20 , 20 20
Part Numb er 560 524 0 1 Rev. A
© 20 20 Telg uard. Telg uard and the Telg uard Lo g o are reg istered trademarks o f
Telular Co rpo ratio n | Telular is a b usiness unit o f AMETEK, Inc . All Rig hts Reserved.
So le Pat h Co m m unicat or

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TG-7FP and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Telguard TG-7FP

  • Page 1 Inst allat io n & Op erat io n Guid e COMPANY CONFIDENTIAL Fo r use b y TELGUARD c usto mers o nly. Distrib utio n to o ther parties stric tly pro hib ited. No vember 20 , 20 20 Part Numb er 560 524 0 1 Rev.
  • Page 2 The Telg uard TG-7FP meets UL and ULC standards fo r Co mmerc ial Fire and Co mmerc ial Burg lary systems. The Telg uard TG-7FP may b e used in Co mmerc ial Fire, Co mmerc ial Burg lary, o r c o mb inatio n Fire/ Burg systems as the so le c o mmunic atio n path, when applic ab le features are enab led.
  • Page 3 Fut ure Test ing and Lim it at io ns o n Use The Telg uard TG-7FP is part o f an advanc ed desig n alarm c o mmunic atio n system. It do es no t o ffer g uaranteed pro tec tio n ag ainst b urg lary and fire. Any alarm c o mmunic atio n system is sub jec t to c o mpro mise o r failure.
  • Page 4 AND HOLD HARMLESS. W A RRA NTY and LIMITA TIONS TELGUARD W ILL REPAIR OR REPLACE ( OUR OPTION) INOPERATIVE UNITS FOR UP TO TW O YEARS FROM DATE OF MANUFACTURE. EXCLUDES DAMAGE DUE TO LIGHTNING OR INSTALLER ERROR AS W ELL AS UNITS THAT INCORPORATE MATERIAL, OR USED IN A MANNER OR ENVIRONMENT, NOT SPECIFICALLY AUTHORIZED IN THIS MANUAL.
  • Page 5: Table Of Contents

    Ste p 1: Re g iste r the Te lg uard Co mmunic ato r Ste p 2: Physic ally Install the TG-7FP in De sire d Lo c atio n Ste p 3: De te rmine Ante nna Plac e me nt fo r Be st Pe rfo rmanc e...
  • Page 6 Po we r Dig ital Ce llular Radio and Othe r Spe c ific atio ns Ap p e nd ix 7 Ac c e sso rie s Telg uard TG-7FP Installatio n & Operating Guide 560 524 0 1 Rev A...
  • Page 7: General Descr Ip T Io N And Op Erat Io N

    DACT interfac e. In suc h c ases, the panel determines the alarm repo rting path. NOTE: W hile wo rking in Canada, TG-7FP-A may use Ro g e rs W ire le ss, Be ll Mo b ility, Te lus , o r SaskTe l ne two rks.
  • Page 8: Info Rmatio N Re Late D To So Ftware Se Tting S

    Central-Statio n Burg lar-Alarm Units, UL 1610 and Standard Line Supervisio n, the TG-7FP must meet these req uirements: The TG-7FP c o mmunic ato r must b e used in o ne o f the fo llo wing c o nfig uratio ns: •...
  • Page 9 • The TG-7FP shall b e used in c o njunc tio n with a ULC o r c -UL Listed Co ntro l Unit/ Alarm Panel, whic h will supply po wer to o perate the c o mmunic ato r.
  • Page 10: Fe Ature S

    No Serv ice Co nd it io n ( NSC) A no servic e c o nditio n (NSC) o c c urs when the TG-7FP is unab le to reg ister with the c ellular netwo rk. NSC c an b e c o nfig ured to trip the superviso ry relay o utput ( STC relay) after a pro g rammab le perio d o f time.
  • Page 11: Link Supe Rvisio N

    The c o mmunic ato r c o ntinuo usly mo nito rs the c irc uit that pro vide s dial to ne to the alarm panel. The TG-7FP will supply 30 VDC b y default b ut c an b e c o nfig ured to supply 4 0 VDC, as needed.
  • Page 12: Te Lg Uard Auto Matic Se Lf-Te St Re Po Rt

    Transmit Disab le c o mmand rec eived fro m TCC: use d whe n a runaway diale r situatio n is de te c te d o r by Custo me r Se rvic e , fo r e xample Telg uard TG-7FP Installatio n & Operating Guide 560 524 0 1 Rev A...
  • Page 13: Po St-Installatio N Re Mo Te Pro G Ramming

    Co m p let e Fact o ry Reset Op t io n A spec ial func tio n within the TG-7FP allo ws yo u to perfo rm a c o mplete Fac to ry Reset o n the c o mmunic ato r.
  • Page 14: Ul And Ulc Co Mplianc E

    Fo r Co mme rc ial Fire installatio ns in Canada, the radio fre q ue nc y warning lab e l ( sup p lie d) must b e affixe d to the o utside fro nt c o ve r o f the TG-7FP de vic e to maintain c o mp lianc e .
  • Page 15: Installatio N

    This installatio n appro ac h pro vides the alarm installer with the easiest and fastest metho d o f pro perly installing a TG-7FP devic e. Please fo llo w the instruc tio ns c arefully and if yo u sho uld need assistanc e o r have any q uestio ns, please c all Telg uard Tec hnic al Suppo rt at 1-80 0 -229-2326 extensio n 9.
  • Page 16: Ste P 2: Physic Ally Install The Tg-7Fp In De Sire D Lo C Atio N

    TCC after a 10 -minute perio d witho ut trip events. St ep 2: Phy sically Inst all t he TG-7FP in Desired Lo cat io n Id ent if y Lo c at io n f o r Placing t he TG- 7FP Dev ice and Mo unt Do no t install the c o mmunic ato r in an area where the g eneral pub lic c o uld reaso nab ly b e within 20 c m ( 8 inc hes) o f the antenna.
  • Page 17: St Ep 3: Det Erm Ine A Nt Enna Placem Ent F O R Best Perf O Rm Ance

    TG-7FP using a supplied 2-po sitio n terminal b lo c k. NOTE: Do no t use a p lug -in adap te r o r o the r no n-p ane l p o we r so urc e o n the TG-7FP.
  • Page 18: Ste P 4: Co Nne C T To Pane L Dact And Ac Tivate

    . The FACP and the Te lg uard c o mmunic ato r must b o th b e lo c ate d in the same ro o m. Trip a zo ne o n the alarm panel and c o nfirm that the TG-7FP enab les the alarm p anel to transmit alarm events o ver the c ellular radio netwo rk.
  • Page 19: Ste P 5: Co Nne C T Supe Rviso Ry Trip Outputs

    If nec essary, repro g ram the alarm panel to send pro p er alarm c o de when tripped b y the c o mmunic ato r o ral as desired . Telg uard TG-7FP Installatio n & Operating Guide 560 524 0 1 Rev A...
  • Page 20: Ste P 6: Co Nne C T And Te St The Trip Input ( O Ptio Nal)

    • No Se rvic e Co nd itio n ( NSC) : Disc o nnec t the antenna fro m the TG-7FP. Chec k to see that the STC LED 2 flashes 4 times and if c o nfig ured, alarm panel will detec t the tripped STC after the selec ted perio d o f time indic ating lo ss o f RF sig nal streng th.
  • Page 21: Ap P E Nd Ix 1 Co Nnec Tio N Guid E

    • So le Path ( TG-7FP is the o nly c o mmunic atio n p ath c o nne c te d to the p ane l) : Ce llular-Only transmissio n with Link supe rvisio n ( 180 -sec , 5-min, o r 60 -min) •...
  • Page 22 Used when the c o mmunic ato r is wo rking in a system that also invo lves a Telc o c o nnec tio n o r ano ther c o mmunic atio n path. In this c ase, b o th the TG-7FP and the alternate c o nnec tio ns are b eing mo nito red b y the Alarm Panel.
  • Page 23: Tampe R Switc H Installatio N Fo R Ul/Ulc Co Mme Rc Ial Burg Lary

    Fo r all UL/ ULC Co mmerc ial Burg lary Installatio ns, a Tamper switc h must b e wired to mo nito r the TG-7FP enc lo sure. The wiring fro m Tamper Switc h to the panel shall b e in a rig id o r flexib le metal c o nduit alo ng with o ther wiring fro m the TG-7FP to the Panel.
  • Page 24: Rj-4 5 Jack Pin A Ssig Nm Ent S

    LED 7 External trip Allo ws an external relay to 6 IN Trip Input relay. trig g er an alarm sig nal. Telg uard TG-7FP Installatio n & Operating Guide 560 524 0 1 Rev A...
  • Page 25: Co Mpatib Le Alarm Pane Ls

    TG-7FP: In o rder fo r the alarm panel to be c o mpatible with the TG-7FP, the alarm panel must be pro g rammed to transmit alarm messag e s to the c entral statio n using o ne o f the fo llo wing no n-extended fo rmats: Pulse Fo rmats: 3+1 pulse;...
  • Page 26: Ap P E Nd Ix 2 Tro Ub Le Sho O Ting Guid E

    This sec tio n pro vides a summary o f all LED indic atio ns and their meaning s, as well as the expec ted b ehavio r o f the TG-7FP under vario us exc eptio n c o nd itio ns.
  • Page 27: Tro Ub Lesho O T Ing Quick Ref Erence Tab Le

    If se ve ral tro ub le c o nditio ns are p re se nt, the STC LED will flash all ap p lic ab le indic atio ns in se q ue nc e . Telg uard TG-7FP Installatio n & Operating Guide...
  • Page 28: Led Indic Ato R Guide Rssi Mo De

    To use the side b utto n, use the pro vided to o l o r an unb ent paper c lip. A simple press and release o f either RSSI b utto n will plac e the TG-7FP in RSSI mo de and ano ther simple press will exit RSSI mo de.
  • Page 29: Ap P E Nd Ix 3 Co Mme Rc Ial Fire So Le Path Installatio N

    Fire panels are typic ally pro vided with two Telc o c o nnec tio ns in o rde r to pro vid e multiple repo rting paths. W ith the TG-7FP having a sing le RJ-4 5 Jac k, o ne o f these Telc o c o nnec tio ns is no lo ng er nec essary fo r UL 864 c o mplianc e when using the TG-7FP as the so le path o f c o mmunic atio n.
  • Page 30: Co Mme Rc Ial Fire 6 -Ho Ur Sup E Rvisio N

    Telg uard TG-7FP Installatio n & Operating Guide 560 524 0 1 Rev A...
  • Page 31: A P P End Ix 6 Det Ailed Sp Ecif Icat Io Ns

    Dig it al Cellular Rad io and Ot her Sp ec if icat io ns The Telg uard TG-7FP radio pro vides data c o nnec tivity o n LTE-M netwo rks. The TG-7FP transc eiver is FCC c o mpliant, meeting all req uirements o f Part 15 and 27 testing . It is also c ertified as c o mpliant to PTCRB req uirements.
  • Page 32: A Ccesso R Ies

    10 0 feet o f lo w lo ss hig h perfo rmanc e antenna c ab le and mo unting b rac ket HGDL-0 Hig h Gain Direc tio nal Antenna EXDL-0 External Omni-Direc tio nal Antenna Telg uard TG-7FP Installatio n & Operating Guide 560 524 0 1 Rev A...