[5/8]
[6/8]
[7/8]
[8/8]
8.4.4
Expert settings - Factory settings
If the selection "Factory settings" in the "Expert menu" is confirmed, the device is reset to the
factory settings.
After confirming, the initial commissioning is started automatically.
■
Data of the factory settings: see chapter 8.4.4 "Expert settings - Factory settings" on page
■
35.
Initial commissioning: see chapter 7.1 "Initial commissioning " on page 19.
■
Product manual 2CKA001473B5267
Switching load
Display the measured
temperature value
Offset
Valve protection
Connected load
To indicate the connected load in Watt: Adjustable in
■
steps of 100 watt.
Yes:
■
– The internal temperature value is displayed.
No:
■
– The internal temperature value is not displayed.
Due to environmental influences, the actual set value
temperature cannot always be attained.
In order to adjust the controller in the best way possible, the
temperature offset can be adjusted accordingly.
Adjustable in steps of 0.1°C.
■
The Offset also affects the displayed internal temperature
value.
YES / NO
If valve protection is activated, the load will be switched
■
on every day at 10:00 for at least 5 minutes.
– This function is important if the standard mode is set to
OFF.
Operation
│35