Bosch AVENAR 4000 FAP-425-O User Manual page 34

Hide thumbs Also See for AVENAR 4000 FAP-425-O:
Table of Contents

Advertisement

34
en | Technical Data
Max. installation
height (observe VdS
guidelines)
Max. permitted air
speed
Min. permitted
storage temerature
Max. permitted
storage temerature
Min. permitted
operating
temperature
Max. permitted
operating
temperature
Permitted relative
humidity
Protecting category
according to
EN 60529
Ring color code
Dimensions without
base
Dimensions with base ⌀ 120 mm x 63.5 mm
Housing material/
color
Approx. weight
without packaging
Approx. weight with
packaging
The FAP-425-O and the FAP-425-OT have the same technical data as the FAP-425-O-R and
FAP-425-OT-R, but are not fitted with rotary switches.
2021-11 | 4 | F.01U.283.550
FAP-425-
FAP-425-
DOTC-R
DOT-R
16 m
20 m/s
-20 °C
-25 °C
+50 °C
+80 °C
-10 °C
-20 °C
+50 °C
< 95 % (non condensing)
IP 41 / IP 43 with detector base with damp room seal
2x yellow
2x black
⌀ 99.5 mm x 52 mm
ABS/white, similar to RAL 9010, matte surface
80 g
75 g
135 g
125 g
User manual
FAP-425-
FAP-425-
DO-R
OT-R
+65 °C
+50 °C
2x grey
1x black
115 g
Bosch Sicherheitssysteme GmbH
AVENAR detector 4000
FAP-425-
FAH-425-
O-R
T-R
7.5 m
-
+65 °C
+50 °C
-
1x red