Diagnostic Data - Bosch AVENAR 4000 FAP-425-O User Manual

Hide thumbs Also See for AVENAR 4000 FAP-425-O:
Table of Contents

Advertisement

30
en | Maintenance and Service
Notice!
i
The test head must remain over the detector until the detector has been triggered. The time
taken to distribute the test aerosol in the test head and therefore the trigger time of the
sensor can be up to 20 seconds.
Simultaneous walktest
On the fire panel, in the Walktest menu, select Simultaneous walktest.
Multisensor detectors can be tested simultaneously with the FME-TESTIFIRE multi-stimulus
test tool. Observe the notes in the detector testing device and fire panel operating
instructions.
Notice!
i
An alarm message is only displayed on the panel if all sensors are triggered during the
simultaneous walktest. If this does not happen, one of the sensors is faulty.
Testing outside the Revision Mode
The FAP-425-DOTC-R detector can be triggered outside of the revision mode only by the
following stimuli:
7.3

Diagnostic data

Optical system value (display of the current pollution level)
0 - 230
0 - 350
350 - 450
450 - 510
2021-11 | 4 | F.01U.283.550
The same test device is used to test the CO sensor in the FAP-425-DOTC-R. You only need
to exchange the test aerosol with the CO testing gas bottle. The testing gas must be
applied for 1/2 to 1 second for the CO test.
The thermal sensor of the FAP-425-DOTC-R / FAP-425-DOT-R / FAP-425-OT-R / FAP-425-
OT is tested with the test device for heat detectors.
Rise of temperature according to the sensitivity settings A2R, A2S, BR, and BS as defined
by EN 54-5
Simultaneous creation of artificial smoke and CO (by a suitable multi-stimulus test tool,
like FME-TESTIFIRE)
Simultaneous creation of artificial smoke and rise of temperature (by a suitable multi-
stimulus test tool, like FME-TESTIFIRE)
Status
Status of the detector: normal, trouble or alarm.
Type
Detector type.
Physical address
Module where the detector or the detector line is installed.
Logical address
Detector installation address.
Example: 10-03 means that the detector is in zone 10 and has the detector number 3.
Optical analog value IR LED, Optical analog value blue LED
Initial set-up value for a new detector
Normal working range
Slight pollution: Exchange detector soon
Heavy pollution: Exchange detector immediately
User manual
AVENAR detector 4000
Bosch Sicherheitssysteme GmbH