Mounting anti-insertion locks Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular with the kit sheet 1SDH001000R0701.
Figure 55
Mounting the fixed part of the
Fasten the fixed part to a horizontal surface using four M8 × 25 screws. The screws are supplied by ABB. See
Figure 56. Tighten the screws with tightening torque = 21 N m - 186 lb in.
withdrawable circuit-breaker
OK
NO
Figure 56
WARNING! Emax E4.2 circuit breakers can only be installed in vertical position
26 | © 2021 ABB | 1SDH002083A1002 - ECN000119014 - Rev. A