Burner control unit
Program sequence during commissioning
qQ
F
qW
C
4
E
6
G
M
3
~
K
8
PTC
A'
Start of oil pre−heat time
A
Start−up
B
Time of flame formation
C
Operating position
D
Controlled switch−off
Burner control unit LOA 14. ...
tw Oil preheat time up to
t1 Pre−purge time
t2 Safety time
t3 Pre−ignition time approx. 13 s
t3n Post−ignition time
after flame builds approx. 15 s
*1
Subject to the temperature of the oil supply.
Initial start−up, inspection and maintenance
t3
t1
tw
*1
12 min.
approx. 13 s
max.
10 s
t2
t3n
3 qW Plug−in terminals on the
burner control unit
C Solenoid valve on the oil pump
E Ignition transformer
F Flame monitor
G Burner motor
K Oil preheater
Burner control unit LMO 14. ...
tw Oil preheat time up to
t1 Pre−purge time
t2 Safety time
t3 Pre−ignition time approx. 15 s
t3n Post−ignition time
after flame builds approx. 13 s
*1
12 min.
approx. 16 s
max.
10 s
17