Burner Control Unit - Viessmann Vitoflame 100 Service Instructions For Contractors

Pressure-jet gas burner for vitoplex 100, 200 and 300 rated output 80 to 225 kw for vitorond 200 rated output 125 to 195 kw
Hide thumbs Also See for Vitoflame 100:
Table of Contents

Advertisement

Burner control unit LME 21....
Program sequence during commissioning
A
Start command
B B'
Interval before the flame has
built
C D
Burner operation
D
Controlled shutdown
1 qW Plug in terminals on the burn-
er control unit
Burner control unit LME 21....
t3
Pre ignition time approx. 2 s
t3n
Post ignition
when a flame is
established
Function and fault displays through indicator lamps (LED)
In standard mode, operating conditions are displayed by colour code through
LED indicators A (see the following table).
The red indicator illuminates permanently after a fault shutdown. In this condi-
tion, the optical fault cause display can be activated (see program sequence on
page 25).
C
D
E
F
G
H
K
t4
approx. 2 s
tw
TSA Safety time after

Burner control unit

Gas pressure switch
Electronic ignition
Burner motor
Fuel valve 1
Fuel valve 2
Air pressure switch
Flame monitoring
Interval stage I
approx. 8 s
II
Dwell time
2.5 s
max. 3 s
expiry
25