Viessmann VITOFLAME 200 Service Instructions Manual page 14

Pressure jet oil burner. up to 40 kw with oil preheater, from 50 kw without oil preheater. for vitorond 200 and vitorond 222
Hide thumbs Also See for VITOFLAME 200:
Table of Contents

Advertisement

Initial start−up, inspection and maintenance
Further details regarding the individual steps
Checking and cleaning the flame monitor
0
B
C
D Strap centring tab
E Flame monitor sight glass
F
14
A
6.0
19.0
D
1. Pull flame monitor A from
flange C.
2. Clean the flame monitor.
Safety check
Burner start with
darkened flame
monitor
Burner start with
E
flame monitor lit
from an outside
source
3. Push flame monitor A into
flange C, until strap B audibly
clicks into place.
Note
Observe the angle and distance.
Safety check
Burner operation
with simulated
flame blow−off:
for this, pull
plug F from the
solenoid valve
during operation
and leave in this
condition
(cont.)
Response
Fault shutdown
at the end of the
safety period
Fault shutdown
after max. 40 s
Response
Restart followed
by fault
shutdown at the
end of the safety
period