Standard values for burner adjustment

Please note
Check that the service instructions are valid for the burner concerned (see
notes on applicability, page 44 and serial no. on the burner type plate).
Rated output
Oil burner nozzle
Make: Fluidics
Make: Danfoss
Oil pressure approx.
Oil flow rate
Air damper setting (s. p. 9)
Blast tube connection (s. p. 9)
Static burner pressure
Aluminium sensor plate baffle
Number of plugs
remaining in the baffle
Rated output
Oil burner nozzle
Make:
Fluidics
Make:
Danfoss
Oil pressure approx.
Oil flow rate
Air damper setting (s. p. 9)
Blast tube connection (s. p. 9)
Static burner pressure
Aluminium sensor plate baffle
Number of plugs
remaining in the baffle
*1
The requirements laid down for the certificate of environmental excellence were
verified only with the nozzles shown.
*2
The oil pressure may vary from that indicated by the values shown, due to nozzle
tolerances and varying oil characteristics.
*3
To check the burner settings.
36
kW
*1
Type
Type
Gph
*2
bar
kg/h
l/h
mm
*3
(s. p. 9)
mbar
mbar
kW
*1
Type
Type
Gph
*2
bar
kg/h
l/h
mm
*3
(s. p. 9)
mbar
mbar
15
18
60ºSF
60ºSF
0.40
0.45
9.0
9.0
1.40
1.68
1.65
1.98
6.0
8.0
2.0
3.0
3.2 3.6
3.2 3.6
0
0
33
40
45ºSF
60ºSR
0.85
1.00
9.0
10.0
3.09
3.74
3.63
4.40
7.5
15.0
7.5
8.0
2.5 3.0
2.5 3.0
0
0
22
27
60ºHF
60ºSR
0.65
0.60
9.0
9.0
2.06
2.53
2.42
2.97
8.5
7.5
5.0
6.0
3.2 3.6
3.0 3.3
0
0
50
63
80ºH
60ºB
1.50
1.00
15.0
9.5
4.68
5.89
5.50
6.93
9.0
12.0
10.0
9.0
3.2 3.7
2.5 3.0
0
0