Operating program
For information on the operating programs, see
page 19
Time program
Further information can be found in chapter
"Terminology" in the Appendix.
Setting a time program
Factory setting: One time phase from 00:00 to 24:00 h
for every day of the week
Tap the following buttons:
1. "Menu"
2. "Heating"
3. "Heating circuit 1", "Heating circuit 2" or "Heat-
ing circuit 3" as the required heating circuit
Heating curve
Further information can be found in chapter
"Terminology" in the Appendix.
Setting the heating curve
Factory setting:
"Slope": 1.4
"Level" of the heating curve: 0
Tap the following buttons:
1. "Menu"
2. "Heating"
3. "Heating circuit 1", "Heating circuit 2" or "Heat-
ing circuit 3" as the required heating circuit
4. "Heating curve"
5. +/
for the required value for "Slope" or "Level"
6. Press OK to confirm
Example: Changing the heating curve slope to 1.5
A graph clearly shows the change in the heating curve
as soon as you alter the value for the slope or level.
(cont.)
Central heating — Multi boiler system control
4. "Time program heating"
5. Press OK to confirm
Procedure for setting a time program, see page 19
Note
When adjusting the setting, bear in mind that your
heating system requires some time to heat the rooms
to the required temperature.
Heating circuit 1 heating curve
Flow temperature
100
75
23 °C
64 °C
50
50 °C
25
36 °C
0
20
10
0
-10
Outside temperature
Fig. 28
Depending on various outside temperatures (shown on
the horizontal axis), the assigned set flow tempera-
tures for the heating circuit are highlighted white.
Slope
Level
91 °C
78 °C
1.5
.
1
-20
-30
OK