Fire-Extinguishing Equipment - Viessmann KOB PYROMAT DYN 45 Instructions For Assembly And Installation

Table of Contents

Advertisement

a) Fire-extinguishing System for Burner Slide-in Module, Art. No. K-SLE / 7387785
Note:
Pyromat-DYN has an extra charge with Art. No. K-SLE (see Spec Sheet 4500)
With PYROT and PYRTEC this is included in the burner article.
N25 level monitoring system
extinguisher water container 25
firing
Fig. 1: K-SLE on feed auger
b) Fire-extinguishing System for Material Feed Facility, Art. No. K-SLV / 7388521
For Köb scope of delivery, refer to Spec Sheet 4500
metering container
with isolating layer
firing
Fig. 2: K-SLV on conveyor auger
Note:
The lines must be executed in metal (1/2") with fixed pipework (K-SLE and K-SLV).
It must not be possible to shut off the cold water inlet without the aid of tools.
Be especially sure to comply with Point 5 of the Installation Instructions (Fire Prevention).
Note:
K-SLV is an alternative or supplementary safety device. As standard, either a slide valve (Art. No. MBA-.; included in
Article ADF_.,. / ADE_3,0) is required for pressureless material storage sites or a rotary valve (Art. No. MBZ-.) for
material storage sites with over- or under-pressure (loading with fan, such as wood-processing businesses).
Köb Holzheizsysteme GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@kob.cc
Spec Sheet

Fire-extinguishing Equipment

K-SLE; K-SLV Installation
material feed facility
KW: cold water inlet
DN 15 (½")
Min. 2.0, max. 3.0 bar
CW
Fig. 3: K-SLV on extractor system situated on top with downpipe
Subject to technical changes
Line from container to the
½" valve (short as possible)
Valve adjustment
Danfoss AVTA 15 50-90°C
3, equivalent to approx. 80° C
CW
metering container
with isolating layer
firing
4550-1
2009-03-01_GB