a) Safety equipment provided by the installing heating engineer
SV...
Safety valve, pressure set max. 3.0 bar, homologated component as per DIN 3440
Nominal width of the valve for the connecting line and the exhaust pipe as per DIN 4751, Part 2
TS...
Thermal run-off safety valve R ¾", homologated component, opening temperature 95-100°C,
(safety heat exchanger built into the burner)
KW...
Cold water inlet DN 15 R ½", metal, fixed pipework, min. 2.5 bar, max. 3.5 bar
TSL...
Drain pipe, thermal run-off safety valve R ¾", (NW 20)
EL...
Air separator (recommended: absorption-type degasser)
ExG...
Expansion tank closed, homologated
(Recommendation: connect on cool return flow, connected to the boiler via the forward flow without any
blockage units)
DAZ...
Pressure gauge (manometer)
TAZ...
Temperature indicator (thermometer)
b) Burner circuit with hydraulically switched heat storage tank
Boiler
Burner circuit pump M20
KPM-DYN
Make: Wilo model
45
EAS 30/6-3-PR-180-12-I VXG48.32/SQS35.00
65
TOP-S 30/7 EM
85
TOP-S 30/7 EM
1)
Connecting thread for inlet
2)
Length of the exhaust pipe up to 4.0 m (for longer lines, see DIN 4751 Part 2)
c) Designation of the motors, sensors and safety switches
Motors:
M1
Exhaust blower
M2
Feed auger
M11
Drive for cleaning/de-ashing
M12
Motor-operated air vent
M13
Motor-operated air vent
M16
Ignition device
M20
Burner circuit pump
Y20
Burner control valve
Safety switches:
N21.1
Temperature-limiting safety switch
S2
Safety limit switch
Maintenance lid for feed auger
d) Recommended design for accumulator,
The hydraulically switched heat storage tank has the following advantages:
Gentle control in automatic operation (increased efficiency, minimal emissions in practical operation)
-
-
Higher performance peaks are possible for the consumers
Log operation is possible (see Operating Instructions)
-
Recommended volume, V
Minimum V
PYROMAT-DYN
[litres]
45
700
65
900
85
1100
Köb Holzheizsysteme GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@kob.cc
Spec Sheet
Wood-burning Pyromat-DYN
Installation, closed system
Modulating valve Y20
Make: Siemens Model
VXG48.32/SQS35.00
VXG48.40/SQS35.00
V
SP:
Recommended V
SP
[litres]
1000
1500
2000
Subject to technical changes
Forward flow
(VL)
Return flow
(RL)
Bypass (BP)
NW 40
NW 40
NW 50
Electrical probes and sensors:
B1G.1
Transmitter light barrier for embers (opposite slide-in
module)
B1G.2
Receiver light barrier for embers (on slide-in module side)
B1
Exhaust gas sensor PT-100
B02
Temperature sensor for feed auger PT-100
B2.1
Transmitter light barrier for feed auger
B2.2
Receiver light barrier for embers
B20
Burner sensor KTY 10/6
B20.1
Return circuit sensor QAZ 21.5220
B26
Lambda sensor
Accumulator with storage management:
Y28
Storage control valve (only with ECO-function)
B28.1
Heat storage sensor, top
B28.2
Heat storage sensor, centre
B28.3
Heat storage sensor, bottom
SP
SP
3950-2
2009-03-01_GB
Safety valve
Safety line SVL
Model SV 68 M 1)
2)
R ¾ "
NW 25
R ¾ "
NW 25
R 1"
NW 32