8. The equipment shall be supplied with Class 2 as defined in article 725.121 or NFPA
5.5
Install conduits and cables
The conduit and cable installation must comply with the following guidelines:
•
To avoid water condensation in the detector, install it with the conduits/cable entries
facing downwards.
•
Use flexible conduits/cables for the last portion connecting to the detector.
•
When pulling the cables through the conduits, ensure that they are not tangled or
stressed. Extend the cables about 12-in. (30 cm) beyond the detector location to
accommodate wiring after installation.
•
After pulling the conductor cables through the conduits, perform a continuity test.