Table 5-2: Minimum Separation Distances
Installation line of sight distance, ft. (m)
98 (30)
131 (40)
164 (50)
197 (60)
5.2.7
Wiring
For wiring, use color-coded conductors or suitable wire markings or labels.
The wire cross-section must be between 28 to 14 AWG (0.5 mm
The selected wire gauge should be based on the number of detectors used on the same
loop and the distance from the control unit. The maximum number of wire
connections in one terminal is two wire cross-sections, each 1 mm
To fully comply with electromagnetic compatibility (EMC) directive and protect against
interference caused by radio frequency interference (RFI) and electromagnetic
interference (EMI), the cable to the detector must be shielded, and the detector must
be grounded. Ground the shield at the detector end.
Rosemount 936
(continued)
Minimum separation, ft. (m)
6.5 (2.5)
11.5 (3.5)
15 (4.5)
16.5 (5)
2
to 2.5 mm