If the product is to be used as a safety related device, an appropriate independent
certification, would be required meeting all the requirements.
4.6
Installing conduits and cables
The conduit and cable installation must comply with the following guidelines:
•
To avoid water condensation in the detector, install it with the conduits/cable entries
facing downwards.
•
Use flexible conduits/cables for the last portion connecting to the detector.
•
When pulling the cables through the conduits, ensure that they are not tangled or
stressed. Extend the cables about 12 in (305 mm) beyond the detector location to
accommodate wiring after installation.
•
After pulling the conductor cables through the conduits, perform a continuity test.
Rosemount 935
Fed directly from cells or batteries.