Figure 5-4: Detector and Tilt Mount Assembly Using Lower Mounting Access
A. Back cover
B. Detector
C. Alignment tool tightening bolt
D. Alignment tool
Table 5-4: Tilt Mount Kit
Item
Tilt mount
Screw
Spring washer
Prerequisites
Prior to mounting the tilt mount to a stable surface, verify that the line of site is
unobstructed and corresponds to the detector's installation distance.
Procedure
1. Place the tilt mount holding plate in its designated location and secure it with four
Rosemount 936
fasteners through four holes with diameters of 0.3-in. (8.5 mm).
NOTICE
Skip this step if the tilt mount is already installed.
Quantity
1
1
1
Installation
October 2021
Type / model
N/A
M10 x 1.5
No. 10
43