Daikin Altherma 3 R F Installer's Reference Manual page 214

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

10
|
Configuration
Sensors
Installer reference guide
214
#
Code
[9.A.1]
[D‑08]
[9.A.2]
[D‑09]
External sensor
#
Code
[9.B.1]
[C–08]
Ext. amb. sensor offset
ONLY applicable in case an external outdoor ambient sensor is connected and
configured.
You can calibrate the external outdoor ambient temperature sensor. It is possible
to give an offset to the thermistor value. This setting can be used to compensate
for situations where the external outdoor ambient sensor cannot be installed on
the ideal installation location.
Description
Electricity meter 1:
0 None: NOT installed
1 1/10kWh: Installed
2 1/kWh: Installed
3 10/kWh: Installed
4 100/kWh: Installed
5 1000/kWh: Installed
Electricity meter 2:
0 None: NOT installed
1 1/10kWh: Installed
2 1/kWh: Installed
3 10/kWh: Installed
4 100/kWh: Installed
5 1000/kWh: Installed
In case of pulse meter for photovoltaic panels:
6 100/kWh for PV panel: Installed
7 1000/kWh for PV panel: Installed
Description
External sensor: When an optional external
ambient sensor is connected, the type of the
sensor must be set.
0 None : NOT installed. The thermistor in the
user interface and in the outdoor unit are used
for measurement.
1 Outdoor: Connected to PCB of the indoor
unit measuring the outdoor temperature.
Remark:
For
some
temperature sensor in the outdoor unit is still
used.
2 Room: Connected to PCB of the indoor unit
measuring the indoor temperature. The
temperature sensor in the user interface is NOT
used anymore. Remark: This value has only
meaning in room thermostat control.
ERGA04~08EA + EHVH/X04+08S18+23EA/EJ
functionality,
the
Daikin Altherma 3 R F
4P629086-1A – 2021.11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents