Daikin Altherma 3 R F Installer's Reference Manual page 204

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

10
|
Configuration
Emergency
Installer reference guide
204
Additional capacity step 2
#
Code
[9.3.5]
[6‑04]
Equilibrium
#
Code
[9.3.6]
[5-00]
[9.3.7]
[5-01]
Operation
#
Code
[9.3.8]
[4‑00]
INFORMATION
When heating of the DHW by the heat pump is too slow, it may affect a comfortable
operation of the space heating/cooling circuit. If so, allow the backup heater to assist
during DHW operation by setting [4-00]=1 or 2.
INFORMATION
Only for systems with integrated domestic hot water tank: If backup heater
operation during space heating needs to be limited but can be allowed for domestic
hot water operation, then set [4‑00] to 2.
Emergency
When the heat pump fails to operate, the backup heater can serve as an
emergency heater. It then takes over the heat load either automatically or by
manual interaction.
When Emergency is set to Automatic and a heat pump failure occurs, the
backup heater automatically takes over the domestic hot water production and
space heating.
Description
The capacity difference between the second
and first step of the backup heater at nominal
voltage. Nominal value depends on backup
heater configuration.
Description
Equilibrium: Deactivate backup heater (or
external backup heat source in case of a bivalent
system) above the equilibrium temperature for
space heating?
0: No
1: Yes
Equilibrium temperature: Outdoor
temperature below which operation of the
backup heater (or external backup heat source in
case of a bivalent system) is allowed.
Range: –15°C~35°C
Description
Backup heater operation:
0: Restricted
1: Allowed
2: Only
DHW: Backup heater operation is
enabled for domestic hot water and disabled
for space heating.
ERGA04~08EA + EHVH/X04+08S18+23EA/EJ
Daikin Altherma 3 R F
4P629086-1A – 2021.11