Reading out electrical
measured variables
EIB Delta-Meter
Electricity Meters
The measured variables are measured again approx. every 5 seconds and
can either be read out in 'Instrument mode' or in Menu mode [4 InStr].
In the case of transformer rated meters all measured variables are
secondary values.
The measuring accuracy of all the values corresponds to the requirements of
the norm IEC 1036 within the supply voltage tolerance of ± 20 % and the
current range of 0.05 I
b
Measured
Tolerance
variable
Frequency
± 2 %*
Voltage
± 2 %*
Current
± 2 %*
Active power
± 2 %*
Reactive power
± 2 %*
Power factor
± 1°
* 1 % for class 1 meters
Up to 24 electrical measured variables can be displayed in Menu mode
[4 InStr], depending on the EIB Delta-Meter. All electrical measured
variables are secondary values.
Button Number Display/comment
'Normal mode' (starting position)
x 1
[3 Error ]
S
x 1
[4 InStr ]
Sc
x 1
S
x n
Scrolls manually through the individual measured
Sc
variables
x 1
Back to [4 InStr]
LSc
x 1
Back to 'Normal mode'
LSc
(nominal current) to I
max
(limit current).
Electrical measured
variables are automatically
displayed (one every 7s).