ABB EIB Delta User Manual page 28

Electricity meters with i-bus eib
Table of Contents

Advertisement

®
ABB i-bus
EIB
Err 113:
Err 115:
Err 116:
Err 118:
Err 119:
Err 120:
Err 121:
Err 122:
Err 123:
Err 124:
Err 125:
Err 126:
Err 127, 128, 129:
Error codes that have not been
mentioned:
EIB Delta-Meter
Electricity Meters
Phase current L3 lies above the given maximum value.
Note: Meter has the wrong nominal current for this application. Wrong
current transformer.
System frequency lies above the given maximum value (> 65 Hz).
System frequency lies below the given minimum value (< 45 Hz).
Two-wire, single-phase meter: Phase angle between the voltage and
current does not lie within the normal range.
Three-wire, polyphase meter: Phase angles between phase voltages L1,
L2 and phase current L1 do not lie within the normal range.
Four-wire, polyphase meter: Phase angles between phase voltage L1 and
phase current L1 do not lie within the normal range.
Note: Polarity of the load current connection has been reversed. Direction of
current flow in the current transformer is incorrect. Phase voltages have been
wrongly connected.
Four-wire, polyphase meter: Phase angle between phase voltages L1 and
L2 does not lie within the normal range.
Note: Phase voltages have been wrongly connected.
Four-wire, polyphase meter: Phase angles between phase voltage L1 and
phase current L2 does not lie within the normal range.
Note: Polarity of the load current connection has been reversed. Direction of
current flow in the current transformer is incorrect. Phase voltages have been
wrongly connected.
Three-wire, polyphase meter: Phase angles between phase voltages L1
and L3 as well as L2 and L3 do not lie within the normal range.
Four-wire, polyphase meter: Phase angle between phase voltage L1 and
L3 does not lie within the normal range.
Note: Phase voltages have been wrongly connected.
Three-wire, polyphase meter: Phase angles between phase voltages L1,
L2 and phase current L3 do not lie within the normal range.
Four-wire, polyphase meter: Phase angle between phase voltage L1 and
phase current L3 does not lie within the normal range.
Note: Polarity of the load current connection has been reversed. Direction of
current flow in the current transformer is incorrect. Phase voltages have been
wrongly connected.
Two-wire, single-phase meter: Negative active power.
Four-wire, polyphase meter: Negative active power in phase L1.
Note: Polarity of the load current connection has been reversed. Direction of
current flow in the current transformer is incorrect. Phase voltages have been
wrongly connected.
Four-wire, polyphase meter: Negative active power in phase L2.
Note: Polarity of the load current connection has been reversed. Direction of
current flow in the current transformer is incorrect. Phase voltages have been
wrongly connected.
Four-wire, polyphase meter: Negative active power in phase L1.
Note: Polarity of the load current connection has been reversed. Direction of
current flow in the current transformer is incorrect. Phase voltages have been
wrongly connected.
Total active power is negative.
Note: Polarity of the load current connection has been reversed. Direction of
current flow in the current transformer is incorrect. Phase voltages have been
wrongly connected.
Internal error. Installation self-test could not be carried out.
Note: Repeat the test. If the error message remains, contact your dealer.
Internal errors. Contact your dealer.