ABB i-bus
EIB
5

General

5.1

Error codes

Err 100:
Err 101:
Err 102:
Err 103:
Err 104:
Err 105:
Err 107:
Err 108:
Err 109:
Err 111:
Err 112:
26
EIB Delta-Meter
Electricity Meters
Once the installation self-test has been carried out, possible errors are
displayed in 'Menu mode'
error codes can have different meanings for two-wire, single-phase meters or
three-wire and four-wire, polyphase meters.
Phase voltage L1 is not avalaible
Note: Phase voltage L1 is not connected
Three-wire, polyphase meter: Not used. (The absence of phase voltage L2
is also reported by phase angle error code 119).
Four-wire, polyphase meter: Phase voltage L2 is not available.
Note: Phase voltage L2 is not connected.
Phase voltage L3 is not available.
Note: Phase voltage L3 is not connected.
Two-wire, single-phase meter: Voltage L1 lies above the given maximum
value.
Three-wire, polyphase meter: Voltage between phase L1 and L2 lies above
the given maximum value.
Four-wire, polyphase meter: Phase voltage L1 lies above the given
maximum value.
Note: Meter has the wrong nominal voltage value for this application. Wrong
voltage transformer.
Risk of damage. Disconnect the voltage immediately.
Two-wire, single-phase meter: Voltage L1 lies below the given minimum
value.
Three-wire, polyphase meter: Voltage between phase L1 and L2 lies below
the given minimum value.
Four-wire, polyphase meter: Phase voltage L1 lies below the given
minimum value.
Note: Meter has the wrong nominal voltage value for this application. Wrong
voltage transformer.
Phase current L1 lies above the given maximum value.
Note: Meter has the wrong nominal current for this application. Wrong
current transformer.
Four-wire, polyphase meter: Phase voltage L2 lies above the given
maximum value.
Note: Meter has the wrong nominal voltage value for this application. Wrong
voltage transformer.
Risk of damage. Disconnect the voltage immediately.
Four-wire, polyphase meter: Phase voltage L2 lies below the given
minimum value.
Note: Meter has the wrong nominal voltage value for this application. Wrong
voltage transformer.
Phase current L2 lies above the given maximum value.
Note: Meter has the wrong nominal current value for this application. Wrong
current transformer.
Three-wire, polyphase meter: Voltage between phase L1 and L2 lies above
the given maximum value.
Four-wire, polyphase meter: Phase voltage L3 lies above the given
maximum value.
Note: Meter has the wrong nominal voltage value for this application. Wrong
voltage transformer.
Risk of damage. Disconnect the voltage immediately.
Three-wire, polyphase meter: Voltage between phase L1 and L2 lies below
the given minimum value.
Four-wire, polyphase meter: Phase voltage L3 lies below the given
minimum value.
Note: Meter has the wrong nominal voltage value for this application.
Wrong voltage transformer.
as installation error codes. The displayed
[3 Error]