Daikin Altherma 3 R F Installer's Reference Manual page 69

Hide thumbs Also See for Daikin Altherma 3 R F:
Table of Contents

Advertisement

Restrictions
PATTERN 1
For PATTERN 1 you only need to comply with the spacing guidelines described in
requirements of the indoor
PATTERN 2 and 3
For PATTERN 2 and 3, additionally to the spacing guidelines described in
4
the indoor
unit" [
 66], you also need to comply with the minimum floor area requirements as described in the
following flow chart. The flow chart uses the following tables:
in a room: indoor
unit"  [
Minimum bottom opening area for natural ventilation: indoor
ERGA04~08EA + EHVH04+08SU18+23EA
Daikin Altherma 3 R F
4P629090-1A – 2021.11
PATTERN 1
See
"PATTERN
4
1" [
 69]
A
Room A (= room where indoor unit is installed)
B
Room B (= adjacent room)
a1
Bottom opening for natural ventilation
a2
Top opening for natural ventilation
4
unit" [
 66].
4
  280],
"16.6  Table 2 – Minimum floor area: indoor
INFORMATION
Multiple indoor units. If two or more indoor units are installed in a room, you must
consider the maximum refrigerant charge that can be released in the room when a
SINGLE leak occurs. Example: If two indoor units are installed in the room, each with
its own outdoor unit, then you have to consider the refrigerant charge of the largest
indoor-outdoor combination.
PATTERN 2
PATTERN 3
See
"PATTERN 2 and
"7.1.3 Installation site requirements of
"16.5 Table 1 – Maximum refrigerant charge allowed
4
unit" [
 281].
7
Unit installation
|
PATTERN 4
4
3" [
 69]
See
"7.1.3  Installation site
4
unit"  [
  281] and
"16.7  Table 3 –
"PATTERN
4
4" [
 71]
Installer reference guide
69