Daikin Altherma 3 R F Installer's Reference Manual page 174

Hide thumbs Also See for Daikin Altherma 3 R F:
Table of Contents

Advertisement

10
|
Configuration
Installer reference guide
174
#
Code
[2.6]
[1-06]
[1-07]
[1-08]
[1-09]
Emitter type
Heating up or cooling down the main zone can take longer. This depends on:
The water volume of the system
The heater emitter type of the main zone
The setting Emitter type can compensate for a slow or a quick heating/cooling
system during the heat up/cool down cycle. In room thermostat control, Emitter
type influences the maximum modulation of the desired leaving water
temperature, and the possibility for usage of the automatic cooling/heating
changeover based on the indoor ambient temperature.
It is important to set Emitter type correctly and in accordance with your system
layout. The target delta T for the main zone depends on it.
Description
Set weather-dependent cooling:
Note: There are 2 methods to set the weather
dependent curve. See
"10.5.2 2-points
4
curve" [
 161] and
"10.5.3 Slope-offset
4
curve" [
 162]. Both curve types require 4 field
settings to be configured according to the figure
below.
T t
[1-08]
[1-09]
[1-06]
[1-07]
T
: Target leaving water temperature (main
t
zone)
T
: Outdoor temperature
a
[1-06]: Low outdoor ambient temperature.
10°C~25°C
[1-07]: High outdoor ambient temperature.
25°C~43°C
[1-08]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
[9‑03]°C~[9‑02]°C
Note: This value should be higher than [1‑09]
as for low outdoor temperatures less cold
water is required.
[1-09]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
[9‑03]°C~[9-02]°C
Note: This value should be lower than [1‑08] as
for high outdoor temperatures colder water is
required.
T a
ambient
temperature.
ambient
temperature.
ERGA04~08EA + EHVH04+08SU18+23EA
Daikin Altherma 3 R F
4P629090-1A – 2021.11