Heat pump convectors – Multiple rooms
ERGA04~08EA + EHVH04+08SU18+23EA
Daikin Altherma 3 R F
4P629090-1A – 2021.11
▪
For more information about connecting the electrical wiring to the unit, see:
-
"9.2 Connections to the outdoor
-
"9.3 Connections to the indoor
▪
For each room, a shut-off valve (field supplied) is installed to avoid leaving water
supply when there is no heating or cooling demand.
▪
A bypass valve must be installed to make water recirculation possible when all
shut-off valves are closed. To guarantee reliable operation, provide a minimum
water flow as described in table "To check the water volume and flow rate" in
"8.5 Preparing water
▪
The user interface integrated in the indoor unit decides the space operation
mode. Mind that the operation mode on each room thermostat must be set to
match the indoor unit.
▪
The room thermostats are connected to the shut-off valves, but do NOT have to
be connected to the indoor unit. The indoor unit will supply leaving water all the
time, with the possibility to program a leaving water schedule.
Configuration
Setting
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
Benefits
Compared with underfloor heating or radiators for one room:
▪
Comfort. You can set the desired room temperature, including schedules, for
each room via the room thermostats.
Setup
A Main leaving water temperature zone
B Room 1
C Room 2
a Heat pump convectors (+ controllers)
4
unit" [
117]
4
unit" [
119]
4
piping" [
98].
0 (Leaving water): Unit operation is
decided based on the leaving water
temperature.
0 (Single zone): Main
B
A
a
6
Application guidelines
|
Value
C
a
Installer reference guide