Daikin Altherma 3 R W Installer's Reference Manual page 47

Hide thumbs Also See for Altherma 3 R W:
Table of Contents

Advertisement

ERGA04~08EA + EHBH/X04+08EF
Daikin Altherma 3 R W
4P629085-1B – 2021.11
Setting
Number of water temperature zones:
#: [4.4]
Code: [7‑02]
In case of heat pump convectors:
External room thermostat for the
additional zone:
#: [3.A]
Code: [C‑06]
Bizone kit installed:
#: [9.P.1]
Code: [E‑0B]
Bizone system type:
#: [9.P.2]
Code: [E‑0C]
Shut-off valve output
Shut-off valve
4
See
"Bizone
kit" [
 227] for more information on configuration of the bizone kit.
Benefits
Comfort.
-
The smart room thermostat functionality can decrease or increase the desired
leaving water temperature based on the actual room temperature
(modulation).
-
The combination of the two heat emitter systems provides the excellent
heating comfort of the underfloor heating, and the excellent cooling comfort of
the heat pump convectors.
Efficiency.
-
Depending on the demand, the indoor unit supplies different leaving water
temperature matching the design temperature of the different heat emitters.
-
Underfloor heating has the best performance with the heat pump system.
6
Application guidelines
|
Value
1 (Dual zone): Main + additional
1 (1 contact): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
2 (Yes): A bizone kit is installed in order
to add an additional temperature zone.
0 (Without hydraulic
separator / no direct pump)
1 (With hydraulic separator /
no direct pump)
2 (With hydraulic separator /
with direct pump)
(See 3 system variations described
above)
Set to follow the thermo demand of the
main zone.
If the main zone must be shut off during
cooling mode to prevent condensation
on the floor, set it accordingly.
Installer reference guide
47