Daikin Altherma 3 R W Installer's Reference Manual page 285

Hide thumbs Also See for Altherma 3 R W:
Table of Contents

Advertisement

4/11
Field settings table
Breadcrumb Field code
Setting name
5.9
[6-00]
Hysteresis
5.A
[6-08]
Hysteresis
5.B
Setpoint mode
└─ WD curve
5.C
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
5.C
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
5.C
[0-0D]
High ambient temp. for DHW WD curve.
5.C
[0-0E]
Low ambient temp. for DHW WD curve.
Tank
5.D
[6-01]
Margin
User settings
└─ Quiet
7.4.1
Activation
└─ Electricity price
7.5.1
High
7.5.2
Medium
7.5.3
Low
User settings
7.6
Gas price
Installer settings
└─ Configuration wizard
└─ System
9.1
[E-03]
BUH type
9.1
[E-05]
Domestic hot water
[E-06]
[E-07]
9.1
[4-06]
Emergency
9.1
[7-02]
Number of zones
└─ Backup heater
9.1
[5-0D]
Voltage
9.1
[4-0A]
Configuration
9.1
[6-03]
Capacity step 1
9.1
[6-04]
Additional capacity step 2
└─ Main zone
9.1
[2-0C]
Emitter type
9.1
[C-07]
Control
9.1
Setpoint mode
9.1
Schedule
9.1
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
9.1
[1-01]
High ambient temp. for LWT main zone heating WD curve.
9.1
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
9.1
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
9.1
[1-06]
Low ambient temp. for LWT main zone cooling WD curve.
9.1
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
9.1
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
9.1
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
└─ Additional zone
9.1
[2-0D]
Emitter type
9.1
Setpoint mode
4P629091-1B - 2021.02
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/W
R/W
R/W
R/W (*2)
R/O (*1)
(*3)
R/W
R/W
R/O (*1)
R/W (*2)
(*3)
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(#) Setting is not applicable for this unit.
Range, step
Default value
2~40°C, step: 1°C
25°C
2~20°C, step: 1°C
10°C
0: Fixed
1: Weather dependent
35~[6-0E]°C, step: 1°C
55°C
45~[6-0E]°C, step: 1°C
60°C
10~25°C, step: 1°C
15°C
-40~5°C, step: 1°C
-10°C
0~10°C, step: 1°C
2°C
0: OFF
1: Quiet
2: More quiet
3: Most quiet
4: Automatic
0,00~990/kWh
1/kWh
0,00~990/kWh
1/kWh
0,00~990/kWh
1/kWh
0,00~990/kWh
0,00~290/MBtu
1,0/kWh
2: 3V (*1)
3: 6V (*2)
4: 9W (*3)
0: No DHW (*4)
2: EKHW (*4)
3: Integrated (*5)
7: EKHWP (*4)
0: Manual
1: Automatic(normal SH/DHW ON)
2: Auto red SH/DHW ON
3: Auto red SH/DHW OFF
4: SH ON/DHW OFF
0: Single zone
1: Dual zone
0: 230V, 1~ (*1) (*2)
1: 230V, 3~ (*2)
2: 400V, 3~ (*3)
0: 1 (*1)
1: 1/1+2 (*2) (*3)
2: 1/2
3: 1/2 + 1/1+2 in emergency
0~10kW, step: 0,2kW
2kW (*2)
3kW (*1)(*3)
0~10kW, step: 0,2kW
0kW (*1)
4kW (*2)
6kW (*3)
0: Underfloor heating
1: Fancoil unit
2: Radiator
0: LWT control
1: Ext RT control
2: RT control
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
0: No
1: Yes
-40~5°C, step: 1°C
-10°C
10~25°C, step: 1°C
15°C
[9-01]~[9-00], step: 1°C
35°C
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
10~25°C, step: 1°C
20°C
25~43°C, step: 1°C
35°C
[9-03]~[9-02]°C, step: 1°C
22°C
[9-03]~[9-02]°C, step: 1°C
18°C
0: Underfloor heating
1: Fancoil unit
2: Radiator
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
Installer setting at variance with
default value
Date
Value
(*1) *3V_(*2) *6V_
(*3) *9W_(*4) EHB*_
(*5) EHV*_
(*6) *X*_(*7) *H*