Storage
Extended Storage
Store the UPS covered and upright in a cool, dry location with the battery fully charged.
•
Remove the REMOTE ON/OFF Bypass Jumper (or turn remote ON/OFF Switch to OFF position). Remove
•
any accessories in the accessory slot and disconnect any cables connected to the computer interface
port to avoid unnecessary draining of the battery.
During extended storage in environments where the ambient temperature is -15°C to +30°C (+5°F to
•
+86°F), charge the UPS battery every 4 months.
During extended storage in environments where the ambient temperature is +30°C to +45°C (+86°F to
•
+113°F), charge the UPS battery every three (3) months.
Page: 19